2018-08-16 08:55:36****CORRECTIONS****
 W.P.B. PERMIT: 18051464
 REVIEWED: AUGUST 15, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SOME OF THE UPLOADED DRAWINGS NAMING DESIGNATIONS
 DON?T MATCH THE SHEET PROVIDED. PLEASE RE-UPLOAD THE
 FOLLOWING ARCHITECTURAL DRAWINGS TO PROJECT DOX.
 A.01, A.02, A.03, A.04, A3.3, A3.4, A5.6 AND A5.7
  
 2. ALL CIVIL DRAWINGS WERE UPLOADED STARTING WITH THE
 SAME THREE DIGIT DESIGNATION AS ARCHITECTURAL DWG?S.
 THIS HAS CAUSED THE ARCHITECTURALS AND CIVIL PLANS TO
 GET MIXED IN TOGETHER.
 THE THREE DIGIT PREFIX SHOULD START AT 001 AND 001
 SHOULD NOT BE REPEATED.
 CIVIL PLANS SHOULD HAVE BEEN 001-021
 ARCHITECTURAL WOULD START AT 022
 TO FIX THIS WITHOUT RELOADING ALL PLANS PLEASE DELETE
 ALL CIVIL FILES (C1 THRU C21)RELOAD ALL CIVIL PLANS
 WITH THE FIRST THREE DIGIT AS 000. THIS WILL PUT THEM
 ALL AT THE TOP OF LIST, AND THE REST OF THE DRAWINGS
 WILL KEEP CURRENT DESIGNATIONS.
  
 3. SHEET C21 REFERENCES 2014 CODE FOR WIND LOADS.
 PLEASE UPDATE TO FBC 2017 6 TH EDITION WHEN SUBMITTING
 FOR SITE LIGHTING PERMIT.
  
 4. [FBC 107.2.5]PLEASE UPLOAD THE SURVEY TO SUPPORTING
 DOCUMENTS.
  
 5. A UNITY OF TITLE WILL BE NEEDED TO COMBINE THE TWO
 LOTS TOGETHER. CURRENTLY THERE ARE TWO PCN'S AND TWO
 ADDRESSES
  
 6. DEMO PERMIT FOR FUEL TANKS NEEDS TO BE CLOSED OUT
 PRIOR TO PERMIT ISSUANCE.
  
 7. THE STRUCTURAL REPORT IS A MULTI PAGE DOCUMENT. THE
 FIRST 55 PAGES ARE GOOD, BUT THE REMAINING 35 PAGES
 DON?T SHOW UP. PLEASE VERIFY THAT ALL 80 PAGES ARE
 PRESENT IN THE DOCUMENT AND RE-UPLOAD TO PROJECT DOX IF
 NEEDED.
  
 8. THE GEOTECHNICAL REPORT SITE PREPARATION MENTIONS
 THE REMOVAL OF TANKS. DOES THE REPORT STATE HOW TO
 HANDLE THE INFILL FROM SUCH A LARGE EXCAVATION? THIS
 OCCURS UNDER THE BUILDING SITE AND THE REPORT SHOULD
 ADDRESS HOW TO ACHIEVE THE 3000PSF REQUIRED.
  
 9 SEPARATE PERMITS WILL BE REQUIRED FOR SEPARATE
 STRUCTURES.
 DRIVE THRU CANOPY, DUMPSTER ENCLOSURE, FENCE(IF
 APPLICABLE), LANDSCAPING, SITE LIGHTING(PROVIDE POLE
 WIND CALCS) AND ENGINEERING TO PERMIT CIVIL WORK.
  
 10. SHEET A1.1 DETAIL CALL OUTS 2/A7.4 AND 3/A74 APPEAR
 TO BE FOR SIDE SUPPORT OF THE COILING DOOR, BUT THEY
 LEAD TO DETAIL OF SCALA SIGNAGE.
 UPDATE DETQAIL CALLOUTS AND PROVIDE DETAIL THEY WERE
 INTENDED TO SHOW.
 IS ANY ADDITIONAL SUPPORT NEEDED FOR THE DOOR AND MOTOR
 SUPPORTED ABOVE, IF SO PLEASE UPDATE STRUCTURAL TO
 INCORPORATE.
  
 11. SHEET S0.1 DESIGN AND LOADING. UPDATE THE CODE
 REFERENCE TO FBC 2017 6 TH EDITION.
  
 12. SHEET S.02 IN WIND DESIGN DATA ? UPDATE THE CODE
 REFERENCE TO FBC 2017 6 TH EDITION.
  
 13. PROVIDE ROOF DECKING ATTACHMENT/SPACING SCHEDULES
 FOR THE FLAT ROOF AND THE TOWER ROOF IN APPLICABLE
 ZONES FROM S0.2 WIND DATA SHEET. SECTIONS AND DETAILS
 SHOW SHEATHING DIFFERENTLY. UPDATE TO SHOW SHEATHING AS
 INTENDED.
  
 14. ROOF SUB PERMIT WILL BE REQUIRED(SEE ROOFING REVIEW
 FOR COMMENTS)
  
 15. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED
 SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION.
 KAWNEER DOORS DON?T PROVIDE FOR WATER INFILTRATION.
 PLEASE PROVIDE REQUIREMENTS SET FORTH WATER
 INFILTRATION.
 [FBC 1710.5.1.1]EXTERIOR WINDOWS AND DOORS (HABITAL
 SPACES). (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE
 THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED
 NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG
 RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 16. PROVIDE ROOF DRAINAGE CALCULATIONS, OR IN RESPONSE
 LET ME KNOW WHERE THEY ARE.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  