| 2018-07-26 17:48:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18051461 |
| | 7/26/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE HEAT LOAD SUMMARY SHEET INDICATES A TOTAL |
| | SENSIBLE MBH OF 408, HOWEVER THAT VALUE APPEARS TO BE |
| | THE TOTAL MBH OF THE SYSTEM- PLEASE CORRECT. |
| | |
| | 2) THE ENERGY COMPLIANCE REPORT INDICATES A HEATING |
| | SYSTEM AT 11608 BTUH CAPACITY FOR RTU-1, HOWEVER THE |
| | SCHEDULE ON SHEET M-001 DOES NOT SHOW ANY DATA FOR |
| | HEAT. |
| | |
| | 3) SHEET M001: THE VENTILATION CALCULATION FOR THE |
| | PREFUNCTION CORRIDOR SHALL BE BASED ON AN OCCUPANT LOAD |
| | OF 30 PERSONS PER 1000 SQ. FT. PER TABLE 403.1.1 FBC M. |
| | PLEASE CORRECT THE CALCULATION. |
| | |
| | 4) IN ACCORDANCE WITH SECTION C403.2.6.1 FBC EC DEMAND |
| | CONTROLLED VENTILATION IS REQUIRED IN THE BALLROOM, |
| | BOARDROOM AND PREFUNCTION AREA. |
| | |
| | 5) IN ACCORDANCE WITH SECTION C403.2.7 FBC EC, AN ERV |
| | IS REQUIRED FOR THE NEW AC SYSTEM. |
| | |
| | 6) SHEET M200: PROVIDE COMPLETE STRUCTURAL ENGINEERING |
| | FOR INSTALLATION OF THE RTU USING THE CORRECT WINDSPEED |
| | OF 170 MPH AND DESIGN CRITERIA BASED ON THAT SPEED. |
| | PLEASE CORRECT THE NOTES INDICATING 140 MPH- SECTION |
| | 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |