| 2018-06-28 13:28:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A020 - THERE ARE A PAIR OF DOUBLE DOORS |
| | LEADING OUT OF THE BALL ROOM, 151A & 151B. THIS IS A |
| | MIXED NON-SEPARATED OCCUPANY. THE BALL ROOM IS AN |
| | ASSEMBLY SPACE. |
| | |
| | PER NFPA 101, CHAPTER 12, NEW ASSEMBLY, |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | |
| | THERE IS NO INDICATION OF PANIC HARDWARE FOR THESE |
| | DOOR. |
| | |
| | THERE IS AN INDICATION OF HARDWARE SET 4, PUT THE |
| | HARDWARE DETAILS COULD NOT BE READILY INDETIFIED IN THE |
| | PLAN SHEETS. |
| | |
| | PLEASE PROVIDE DETAILS FOR THESE DOORS THAT MEET THE |
| | REQUIRMENTS OF THE CODE. |
| | |
| | |
| | |
| | 2) ELECTRICAL SHHETS - THERE ARE INDICATIONS OF FIRE |
| | ALARM EQUIPMENT; HOWEVER, NO INDICATIONS OF FIRE ALARM |
| | WORK OR SHOP DRAWINGS. |
| | |
| | ALL WORK ON ANY FIRE ALARM EQUIPMENT OF SYSTEM SHALL BE |
| | DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIE AN APPLICABLE NOTE. |
| | |
| | |
| | |
| | 3) SHEET A002 - THERE ARE CHAIRS INDICATED IN THE BALL |
| | ROOM. ARE THESE CHAIRS PERMANENT. TEMPORARY, LOOSE OR |
| | INTERLOCKING? |
| | |
| | PLEASE PROVIDE CHAIR DETAILS. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |