| 2018-08-12 12:39:00 | ****CORRECTIONS**** |
| | REVISED 8/13 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. A002, FBC B 1004, 100 SF PER OCCUPANT IS SHOWN FOR |
| | ONE OF THE PRE-FUNCTION AREAS, AND 15 SF PER PERSON FOR |
| | THE PREFUNCTION LOUNGE. ALTHOUGH LABELED WITH DIFFERENT |
| | ROOM DESIGNATIONS ("PRE-FUNCTION" VS "PREFUNCTION |
| | LOUNGE") THEY APPEARS TO BE THE SAME. EITHER REVISE |
| | PRE-FUNCTION TO HAVE OCCUPANT LOAD OF 1/15 SF OR SEND |
| | AN EMAIL WITH RATIONALE TO GET THIS RESOLVED PRIOR TO |
| | RESUBMITTAL. IT IS ACKNOWLEDGED THAT THE DIFFERENCE IN |
| | OCCUPANT LOAD WILL NOT AFFECT EGRESS, BUT DISCREPANCY |
| | SHOULD BE CORRECTED OR EXPLAINED. |
| | |
| | 2. A002, DOOR 1, SEE FBC A 404.2.6, DOORS IN A SERIES, |
| | AND REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 3. NA |
| | |
| | 4. FBC B 1010.1.10, THE DOUBLE DOORS 151A AND 151B |
| | INDICATES HARDWARE SET 4, NO PANIC BARS PROPOSED. I WAS |
| | UNABLE TO LOCATE HARDWARE SET 4; COMPLIANCE NOT CLEAR; |
| | REVISE PLAN ACCORDINGLY. |
| | |
| | 5. FBC CHAPTER 10, DOOR 150A IS SHOWN ON THE DEMO PLAN |
| | AS SWINGING FROM THE MAIN LOBBY/ATRIUM TOWARDS THE |
| | ASSEMBLY AREA. IT NOW SWINGS THE OTHER DIRECTION, AND |
| | IS SHOWN AS HAVING AN EGRESS CAPACITY OF 360, OCCUPANT |
| | LOAD OF 40. |
| | |
| | PLEASE REVISE PLAN TO CONFIRM THAT THIS DOOR WAS NOT |
| | USED FOR EXITING FROM THE LOBBY AND ATRIUM, AS CHANGING |
| | DOOR SWING NOW MAKES THIS SWING AGAINST EGRESS TRAVEL. |
| | |
| | REVISE THE PLAN TO CONTINUE MEANS OF EGRESS SHOWN WHICH |
| | NOW DIRECTS SOME OCCUPANTS THROUGH THE MAIN LOBBY. IT |
| | IS NOT CLEAR IF THAT AREA CAN ACCOMMODATE EXITING FOR |
| | ADDITIONAL OCCUPANTS. TRAVEL DISTANCE FOR THOSE |
| | OCCUPANTS IS NOT CLEAR AS THE EXIT IS NOT SHOWN ON THE |
| | LIFE SAFETY PLAN. |
| | |
| | 6. FBC EB 701.3, THIS STRUCTURE IS LOCATED IN A SPECIAL |
| | FLOOD HAZARD AREA. PROVIDE CUMULATIVE FIVE YEAR VALUE |
| | OF IMPROVEMENTS AND VALUE OF STRUCTURE. IT APPEARS THAT |
| | THE BUILDINGS ARE CONNECTED BY AN ATRIUM, SO IS |
| | CONSIDERED ONE BUILDING. PLEASE CONTACT ME FOR |
| | ASSISTANCE. |
| | |
| | A COMPLETE REVIEW CANNOT BE DONE UNTIL IT IS DETERMINED |
| | WHETHER OR NOT THIS IS CONSIDERED A "SUBSTANTIAL |
| | IMPROVEMENT". OUR ORDINANCE REQUIRES THAT FIVE YEARS OF |
| | IMPROVEMENTS ARE CONSIDERED. |
| | |
| | IF AN ELEVATION CERTIFICATE IS AVAILABLE FOR THIS |
| | STRUCTURE, PLEASE SEND TO ME VIA EMAIL. |
| | |
| | |
| | |
| | |
| | |
| | |