| 2018-09-11 08:38:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE GENERATOR PAD ENGINEERING DOCUMENTS DO NOT HAVE |
| | THE ORIGINAL HANDWRITTEN SIGNATURE OF THE ENGINEER ON |
| | THE SEAL. FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY |
| | SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED |
| | AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION |
| | 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MAY BE |
| | PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN |
| | BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | |
| | 2) THE WIDTH DIMENSION FOR THE 20KW GENERATOR LISTED IN |
| | THE MANUFACTURER'S SPECIFICATIONS EXCEEDS THE MAXIMUM |
| | UNIT DIMENSION THAT IS ALLOWED BY THE PAD ENGINEERING. |
| | FBC 107.2.1 |
| | |
| | 3) THE MINIMUM WEIGHT FOR THE UNIT THAT IS REQUIRED BY |
| | THE PAD ENGINEERING IS 535 LBS. AND THE WEIGHT FOR THIS |
| | UNIT IS 500 LBS. PER THE MANUFACTURER'S SPECIFICATIONS. |
| | FBC 107.2.1 |
| | |