2018-08-09 15:17:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. C5 WIND SPEED IS SHOWN AS 160 MPH (VULT), RISK
 CATEGORY II. ADVISE HOW THIS WAS DETERMINED; IF RISK
 CATEGORY II THIS SHOULD BE A MINIMUM OF 167, AND 179
 FOR RISK CATEGORY III-IV. FBC B 1609.
  
 2ND REVIEW, NOT ADDRESSED. PLEASE REVISE TO A MINIMUM
 OF 167MPH, EXPOSURE C.
  
 2-3. OK
  
 NEW COMMENT: INFORMATIONAL ONLY - A CONTRACT WAS
 PROVIDED. IT APPEARS THAT LANDSCAPING, FENCING WAS
 INCLUDED IN THE VALUE OF THIS PERMIT. BOTH SHOULD BE A
 SEPARATE PERMIT WITH SEPARATE FEES. VALUE HAS BEEN
 ADJUSTED, RESULTING IN A CREDIT.
  
 PLEASE SUBMIT AN APPLICATION FOR EITHER LANDSCAPING OR
 FENCING AT THIS TIME SO THE CREDIT CAN BE TRANSFERRED.
 IF THE PERMIT DOCUMENTS FOR THESE ITEMS ARE NOT YET
 AVAILABLE, A PERMIT APPLICATION NUMBER CAN STILL BE
 GENERATED (WITH A PERMIT APPLICATION) AND WILL BE
 RETAINED AT THE BUILDING DIVISION UNTIL THE TIME THAT
 YOU ARE READY TO PROVIDE PERMIT DOCUMENTS.
  
  
  
  
  