| Plan Review Notes For Permit 18051411 |
| Permit Number |
18051411 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-16 18:13:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. C5 WIND SPEED IS SHOWN AS 160 MPH (VULT), RISK | | | CATEGORY II. ADVISE HOW THIS WAS DETERMINED; IF RISK | | | CATEGORY II THIS SHOULD BE A MINIMUM OF 167, AND 179 | | | FOR RISK CATEGORY III-IV. FBC B 1609. | | | | | | 2. C5, RISK CATEGORY IS SHOWN AS II. SEE FBC B TABLE | | | 1604.5, THIS APPEARS TO BE RISK CATEGORY IV ("OTHER | | | FACILITIES REQUIRED FOR EMERGENCY RESPONSE"). | | | | | | 3. THE STRUCTURAL ENGINEER PROVIDED CALCULATIONS AND | | | DESIGN FOR A POLE DESIGNED TO ANSI/TIA 222 G2. THIS IS | | | IN CONFLICT WITH THE OTHER ENGINEER'S DESIGN CRITERIA, | | | PLEASE CORRELATE. | | | | | | |
|