2018-09-19 08:29:132ND REVIEW: FBC 2014 5TH EDITION
 PERMIT 18051383
 PLUMBING COMMENTS
  
 ONLY ONE SHEET 3.1 WAS SUBMITTED. WHEN RESUBMITTING,
 PROVIDE A 2ND SET.
  
 PROVISO
  
 1. PLAN SHT. 3.1 ADD 4; THE HORIZONTAL BRANCH DRAINS
 FOR THE WASHING MACHINES SHALL BE 3" PER MANUFACTURE
 SPECIFICATION FOR STUDOR VENT FOR A WASHING MACHINE AS
 RED LINED ON THE SANITARY ISOMETRIC.
 2. CONTRACTORS COPY PLAN SHT. 3.1 ADD 4. WAS NOT
 INCLUDED IN SUBMITTAL PACKAGE. A SCANNED COPY OF THE
 AFFECTED RED LINED PORTION OF THE PLAN HAS BEEN
 ATTACHED TO CONTRACTOR'S PLAN SHEET 2.1 FOR
 CONTRACTOR'S USE. CONTRACTOR SHALL OBTAIN A SCANNED
 COPY OF FULL RED LINED PLAN SHEET THROUGH THE BUILDING
 DEPARTMENT FOR A FEE.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715
  
  