| 2018-06-03 05:11:04 | 1) CITY RECORDS SHOW THE TOTAL BTU GAS LOAD TO THE |
| | EXISTING GAS APPLIANCES AS 153, 000 NOT 117,000 AS |
| | SHOWN ON THE SUBMITTED GAS DRAWING. REVISE THE |
| | SUBMITTED GAS PLAN TO COMPLY WITH THE EXISTING RECORD |
| | ON FILE.2017 FBC-FUEL GAS SEC.401.4. |
| | 2) CITY RECORDS SHOW THE MOST REMOTE OUTLET TO THE |
| | EXISTING APPLIANCES AS 140 FEET FROM THE POINT OF |
| | DELIVERY. THIS DISTANCE SHALL BE USED IN SIZING THE GAS |
| | SYSTEM. 2017 FBC-FUEL GAS SEC.402.4.1. |
| | 3) THE EXISTING LOAD TABLE NOTES THE EXISTING LOAD AS |
| | 117,000 BTU'S BUT THE GAS DRAWING SHOWS THE EXISTING |
| | LOAD AS 88,000 BTU'S. ????? REVISE THE DRAWING TO |
| | COMPLY WITH COMMENTS # 1 & 2 ABOVE. |
| | 4) THE GAS DRAWING REFERENCES TABLE 402.4 (22) WHICH IS |
| | FOR A 2 PSI PRESSURE BUT YOU HAVE SUBMITTED THE TABLE |
| | FOR A PE LESS THAN 2 PSI SYSTEM 402.4 (21). WHICH IS |
| | IT, 2 PSI OR LESS THAN 2 PSI? |
| | 5) YOU HAVE SUBMITTED SPECIFICATIONS FOR REGULAORS. IF |
| | THIS IS LESS THAN A 2 PSI SYSTEM, WHY THE REGULATORS? |
| | CLARIFY. |
| | 6) IF THIS IS GOING TO BE A 2 PSI SYSTEM, INDICATE ON |
| | THE REGULATOR SPECS THE MODEL BEING INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 7) THE MINIMUM SIZE LINE TO THE EXISTING APPLIANCES |
| | SHALL BE 1 INCH IF THIS IS TO REMAIN A LESS THAN 2 PSI |
| | SYSTEM. CLARIFY. |
| | 8) THE MINIMU SIZE SCH. 40 METALLIC PIPE AT THE OUTLET |
| | OF THE GAS METER SHALL BE 2 INCHES PER TABLE 402.4 (2) |
| | AAT 140 FEET. |
| | 9) THE NEW TOTAL BTU LOAD OF THE SYSTEM IS 434,000 |
| | BTU'S NOT 398,000 AS SHOWN ON THE PLANS. |
| | 10) THE MINIMUM SIZE METALLIC PIPE TO THE GENERATOR |
| | SHALL BE 1 1/4 INCHES PER TABLE 402.4(2) AT 140 FEET |
| | DISTANCE TO THE MOST REMOTE OUTLET ON THE SYSTEM PER |
| | THE EXISTING GAS PLAN. |
| | 11) SUBMIT MANUF. SPECS FOR THE FLEX CONNECTOR FOR THE |
| | GENERATOR. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FLEX CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR |
| | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL |
| | GAS SEC. 411.1.3.2. |
| | 12) THE GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FEET |
| | FROM ANYBUILDING OPENING INCLUDING SOFFIT SCREENS/ATTIC |
| | VENTS. |
| | |
| | NOTE: I HAVE PLACED TWO COPIES OF THE EXISTING GAS PLAN |
| | FROM CITY RECORDS TO BE USED AS A REFERENCE ONLY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |