2018-06-25 11:57:571ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ON THE APPROVED SET OF PLANS IT SHOWED WING WALLS
 NEXT TO WATER FOUNTAIN THE REVISION HAS REMOVED THOSE
 WALLS THE WATER FOUNTAIN SHALL COMPLY WITH 307.2 . PER
 FBC ACC 602.1
  
 2. THE NEW SINK IN THE COVERED PATIO SHALL COMPLY WITH
 FBC ACC 606.2, 606.3
  
 3. THE NEW SINK UNDER THE COVERED PATIO APPEARS TO BE
 OVER 50' FROM THE HOT WATER SOURCE A RECIRCULATION
 SYSTEM WILL BE REQUIRED FOR THE HOT WATER. PER FBC PL
 607.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  