| Plan Review Notes For Permit 18051332 |
| Permit Number |
18051332 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-29 07:37:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. A1, POSSIBLY OTHER PAGES, SOME REVISION CLOUDS ARE | | | LIGHT, OTHERS DARK, SOME NOT NUMBERED. TYPICALLY NEW | | | UNREVIEWED CLOUDS ARE DARK, OLD PREVIOUSLY REVIEWED | | | CLOUDS ARE LIGHT GREY OR REMOVED. IT APPEARS THAT I | | | SHOULD BE REVIEWING REVISION 3 ONLY, BUT SOME REVISION | | | 3 ARE LIGHT, OTHERS DARK, SOME CLOUDS ARE UNNUMBERED, | | | SO IT IS DIFFICULT TO DETERMINE WHAT HAS CHANGED. FBC | | | 107, PLEASE CLARIFY. | | | | | | 2. SEE PLUMBING ACCESSIBILITY COMMENTS AS THEY ARE | | | APPLICABLE FOR BUILDING REVIEW. | | | | | | 3. GATE AT THE WEST CENTER OF THE BUILDING APPEARS TO | | | LACK THE 18" MANEUVERING CLEARANCE REQUIRED, SEE ANSI | | | 117.1 2009 404.2, TABLE 404.2.3.2, FBC A FIGURE | | | 404.2.4.1(A). | | | | | | |
|