Plan Review Notes
Plan Review Notes For Permit 18051332
Permit Number 18051332
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-29 07:37:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. A1, POSSIBLY OTHER PAGES, SOME REVISION CLOUDS ARE
 LIGHT, OTHERS DARK, SOME NOT NUMBERED. TYPICALLY NEW
 UNREVIEWED CLOUDS ARE DARK, OLD PREVIOUSLY REVIEWED
 CLOUDS ARE LIGHT GREY OR REMOVED. IT APPEARS THAT I
 SHOULD BE REVIEWING REVISION 3 ONLY, BUT SOME REVISION
 3 ARE LIGHT, OTHERS DARK, SOME CLOUDS ARE UNNUMBERED,
 SO IT IS DIFFICULT TO DETERMINE WHAT HAS CHANGED. FBC
 107, PLEASE CLARIFY.
  
 2. SEE PLUMBING ACCESSIBILITY COMMENTS AS THEY ARE
 APPLICABLE FOR BUILDING REVIEW.
  
 3. GATE AT THE WEST CENTER OF THE BUILDING APPEARS TO
 LACK THE 18" MANEUVERING CLEARANCE REQUIRED, SEE ANSI
 117.1 2009 404.2, TABLE 404.2.3.2, FBC A FIGURE
 404.2.4.1(A).
  
  