| Plan Review Notes For Permit 18051322 |
| Permit Number |
18051322 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-03 06:00:37 | 1) ) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE PRESSURE REGULATORS. THE | | | REGULATORS SHALL BE IN COMPLIANCE WITH 2017 FBCR-SEC. | | | G2421.1, G2421.2 (1-7). IDENTIFY WHICH MODEL REGULATOR | | | IS BEING INSTALLED. | | | 2) THE SHUTOFF VALVE FOR THE EXISTING PIPING INTO THE | | | STRUCTURE SHALL BE LOCATED UPSTREAM (AHEAD) OF THE MP | | | REGULATOR PER 2017 FBC-FUEL GAS SEC. 409.4, 2017 | | | FBC-RES. SEC. G2420.4. | | | 3) A REGULATOR IS REQUIRED AT THE EXISTING POOL HEATER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | | | | | | | | | | |
|