| Notes |
| Date |
Text |
| 2018-07-30 07:26:08 | 1) EXISTING GAS PLANS IN CITY RECORDS SHOW THE LONGEST | | | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS | | | 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF | | | THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1. | | | 2) EXISTING GAS PLAN ON FILE WITH THE CITY SHOWS A 1 | | | INCH LINE TO THE INTERIOR EXISTING GAS FIXTURES BUT THE | | | SUBMITTED GAS DRAWING SHOWS A 3/4 INCH LINE. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|