| Notes |
| Date |
Text |
| 2018-05-25 16:17:53 | 05/25/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH | | | COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS | | | NOT ON THE APPROVED DEVICE LIST PUBLISHED BY THE | | | UNIVERSITY OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT | | | DEPARTMENT OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT | | | 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE | | | PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY | | | REQUIREMENTS.YOU CAN REFER TO THEIR CROSS CONNECTION | | | MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/ | | | PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN | | | ECTION-CONTROL-MANUAL FOR MORE INFORMATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | | | | | | | |
|