| 2018-10-07 09:02:40 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES |
| | NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES |
| | WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220, |
| | 408.30; FBC RE E3602.2 (A LOAD CALCULATION SHOULD SHOW |
| | ALL LOADS AND THE CORRESPONDING VA FOR THAT LOAD. THIS |
| | SHOULD BE COMPLETED IN THE FORMAT PROVIDED IN THE FBC |
| | RESIDENTIAL. THE PARTIAL LOAD CALCULATION PROVIDED IS |
| | NOT ACCEPTABLE.) |
| | 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER |
| | PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND |
| | DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE. |
| | PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5, |
| | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 (WHAT IS SHOWN ON THE RISER |
| | DIAGRAM IS NOT THE SAME AS SHOWN ON PLAN. PROVIDE |
| | CORRECTION. RISER DIAGRAM SHOWS A FEED FROM THE METER |
| | TO THE INTERIOR PANEL WHICH IS LOCATED IN THE UTILITY. |
| | CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| | DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE |
| | IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE |
| | OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB. |
| | PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6 |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | NEW COMMENT: |
| | |
| | 7. PLEASE BE ADVISED THAT THESE COMMENTS HAVE NOT BEEN |
| | ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT REVIEW, |
| | IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN |
| | FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS |
| | REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. THE ADDITIONAL |
| | FEE FOR THIS PLAN WILL BE $950.00 . FS 553.80(2)(B) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6742 |