| 2018-09-07 12:55:28 | REVIEW COMPLETED BY JERALD SMITH 0017-P |
| 2018-09-06 12:30:35 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18051263 |
| | PLUMBING COMMENTS: |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE |
| | THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | A. DETAIL A, AS PREVIOUSLY NOTED PLEASE SHOW FLOOR |
| | DRAIN ON SANITARY ISOMETRIC AND FLOOR PLAN; IF NOT |
| | REQUIRED THEN PLEASE REMOVE DETAIL. |
| | B. DETAIL H, IF WATER HEATER IS EXISTING, PLEASE |
| | REMOVE DETAIL. IF NEW WATER HEATER IS REQUIRED THEN A |
| | VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER |
| | (SHOWN). PER FBC RES P2804.7 |
| | 2. SHT. P.1 AND SHEET P.3, FBC RES P3005.4.1 ALLOWS |
| | MAXIMUM 6 DFU ON 2" HORIZONTAL FIXTURE BRANCH. DFU LOAD |
| | ON THE FIXTURE BRANCH SHOWN ON ISOMETRIC AND FLOOR PLAN |
| | CONNECTING KITCHEN SINK/DISHWASHER AND THE WASHING |
| | MACHINE FIXTURE DRAINS IS 7 DFU. SIZE OF FIXTURE BRANCH |
| | MUST BE INCREASED TO ACCOMMODATE THE DFUS ON THE |
| | BRANCH. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |