| 2018-06-20 15:19:27 | MECHANICAL PLAN REVIEW FAIL |
| | |
| | 1 - NEED MANUAL J |
| | |
| | PER 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, |
| | SIXTH EDITION |
| | |
| | R403.7.1EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT |
| | SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE |
| | LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING |
| | EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR |
| | GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR |
| | THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS |
| | INSTALLED. |
| | |
| | 2 - NEED ENERGY COMPLIANCE WORKSHEET |
| | |
| | PER 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, |
| | SIXTH EDITION |
| | |
| | R101.5.1COMPLIANCE MATERIALS. THE FLORIDA BUILDING |
| | COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE, |
| | WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR |
| | MATERIALS THAT MEET THE INTENT OF THIS CODE. COMMISSION |
| | APPROVED CODE COMPLIANCE DEMONSTRATION FORMS CAN BE |
| | FOUND IN TABLE R101.5.1. |
| | |
| | |