| 2018-06-25 10:31:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES |
| | NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES |
| | WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220, |
| | 408.30; FBC RE E3602.2 |
| | 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER |
| | PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND |
| | DISCONNECT LOCATED OUTSIDE, AND A 125 AMP PANEL INSIDE. |
| | PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5, |
| | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 3. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. PLAN |
| | ONLY SHOWS THIS IN ONE OF THE BATHROOMS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| | E3703.4, E3901.6 |
| | 4. BREAKER FOR WATER HEATER IS SHOWN AS 50 AMP. FOR THE |
| | LOAD SPECIFIED OF 4500 WATTS, A BREAKER OF 25 OR 30 |
| | AMPS SHOULD BE USED. PROVIDE CORRECTION. NEC 422.13, |
| | 240.4; FBC RE E3702.11 |
| | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 6. ALL COUNTER TOP RECEPTACLES IN KITCHEN REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.6 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |