| 2018-06-29 17:36:29 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18051263 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS |
| | REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT |
| | SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED. |
| | |
| | AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET |
| | OF PLANS TO TAKE TO THE COUNTY. |
| | |
| | 561-233-5025 FOR MORE INFORMATION |
| | |
| | 2. NOTICE OF ACCEPTANCE(N.O.A.) |
| | N.O.A. 14-0610.05 IS EXPIRED. PLEASE PROVIDE TWO COPIES |
| | OF UPDATED N.O.A. |
| | |
| | 3. SHEET A-5 REFERENCES N.O.A. NO. 17-1018.05 FOR |
| | WINDOWS. PROVIDE N.O.A. FOR WINDOWS AND MULL BAR. |
| | HAVE THE DESIGNER OF RECORD MARK THE SELECTED WINDOWS, |
| | ATTACHMENT TYPE AND STAMP AS REVIEWED. |
| | |
| | 4. SUPPLY ROOFING PRODUCT APPROVAL, OR INDICATE ON YOUR |
| | COMMENT RESPONSE SHEET THAT THEY WILL BE A SUBMITTAL AT |
| | A LATER DATE. |
| | |
| | 5. [FBC R401.2] DETERMINE UPLIFT THAT THE FOOTER WILL |
| | RESIST FOR LIGHT FRAME CONSTRUCTION USING TABLE R401.1. |
| | PROVIDE TYPE OF CONNECTOR AT BASE PLATE FOR THE |
| | DETERMINED UPLIFT, OR SHOW ON CONNECTOR SCHEDULE HOW |
| | THE SST-MST16 MEETS NAILING REQUIRMENTS. |
| | |
| | 6. [FBC R403.1.4]FOOTER TO HAVE MINIMUM 12" DEPTH BELOW |
| | GRADE AND 4" ABOVE GRADE. |
| | |
| | 7. [FBC R401.3]PROVIDE DRAINAGE FROM FOUNDATION AS |
| | OUTLINED IN R401.3 |
| | |
| | 8. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO |
| | BE USED TO MEET REQUIREMNETS OF R703.4 |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS |
| | SUBMITTED AND A COMMENT RESPONSE SHEET. |
| | |
| | |
| | |
| | |