Plan Review Notes
Plan Review Notes For Permit 18051251
Permit Number 18051251
Review Stop B
Sequence Number 4
Notes
Date Text
2018-08-11 17:30:49****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
  
 1. FBC 107.1 THE SCOPE OF WORK IS NOT CLEAR; THE
 DRAWING SHOWS AREA OF DEMO WORK AND PROPOSED WORK UNDER
 THIS PERMIT APPLICATION.
  
 2. FBC 107.1 THE SUBMITTED WALL DETAIL IS NOT CLEAR AS
 TO THE TOP CONNECTIONS OF WALL. DOES THE WALL GO TO THE
 CEILING? IF THAT IS THE CASE A MECHANICAL PERMIT MAY BE
 REQUIRED FOR AN APPROVED VENTILLATION SYSTEM. IF THE
 WALL DOES NOT CONNECT TO THE CEILING ARE THERE
 CONNECTING BRACES ABOVE AND/OR ARE THERE CONNECTIONS TO
 THE EXISTING STRUCTURAL COLUMNS?
  
 3. FBC 107.1 THE GOVERNMENT CODE SHOWN ON THE PLAN IS
 FROM THE FBC 2010. THIS NEEDS TO BE CHANGED TO THE FBC
 2017.
  
 4. FBC 1016.2 PLEASE LABEL EACH ROOM AREA FOR
 DESIGNATION AND OCCUPANT LOAD/OCCUPANT CLASSIFICATION.
 (THE DIRECTIONAL INDICATORS FOR THE PATH OF EGRESS IN
 AREA LABELED AS UNIT "B" IS IN CONFLICT WITH THIS
 SECTION OF CODE).
  
 5. F.S. 481 DOCUMENTS PREPARED BY AN ARCHITECT AND
 SUBMITTED ON PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 AND DATED ORIGINALS.
  
  
  