| 2018-06-22 10:40:57 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18051242 |
| | 6/22/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M401: EXHAUST VENTILATION AT A RATE OF 0.25 |
| | CFMS PER SQ. FT. IS REQUIRED FOR THE FITTING ROOMS PER |
| | TABLE 403.3.1.1 FBC M. |
| | |
| | 2) M401: CORRECT KEYED NOTE #1 WHICH IS INDICATING |
| | EXISTING DUCT SMOKE DETECTOR IN THE RETURN DUCTWORK- |
| | THE #1 NOTES ON THE PLAN ARE POINTING AT THE DETECTORS |
| | IN THE SUPPLY DUCTWORK WHICH ARE THE REQUIRED LOCATIONS |
| | PER SECTION 606.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |