| 2019-02-15 09:26:21 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 4TH REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | ADVISORY: |
| | F.S. 553.80 (2) (B) |
| | (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| | |
| | THE FOLLOWING COMMENTS HAVE NOT BEEN ADDRESSED FROM |
| | PREVIOUS REVIEWS. |
| | |
| | |
| | 1. OK. |
| | |
| | 2. [FBC R301]PROVIDE 2 COPIES OF SURVEY THAT WILL |
| | INDICATE THE UTILITY EASEMENT ON THE SOUTH SIDE OF |
| | PROPERTY. IF ANY PART OF NEW GARAGE ENCROACHES INTO THE |
| | EASEMENT THEN MOVE GARAGE LOCATION ACCORDINGLY OR |
| | OBTAIN EASEMENT CONSENTS FROM EASEMENT HOLDERS. |
| | 2-4. SURVEY NOT PROVIDED. |
| | |
| | 3-9. OK. |
| | |
| | 10. [FBC R301.1.2]PROVIDE NOTICE OF APPROVAL(N.O.A.) |
| | FOR ALL WINDOWS, DOORS AND GARAGE DOORS. IF ANY GLAZING |
| | IS NON-IMPACT RATED THEM PROVIDE PROPOSED PROTECTION |
| | AND ATTACHMNET AS OUTLINED IN R301.1.2. |
| | 10-4. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT |
| | RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE |
| | DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE |
| | TO BE DEFFERED. |
| | |
| | 11-15 OK. |
| | |
| | 16. [FBC 107.2.1]PROVIDE PRODUCT APPROVALS FOR ROOFING |
| | MATERIALS. FOR THE FLAT ROOF, INDICATE ASSEMBLY |
| | PROPOSED AND PROVIDE ENGINEERING IF ASSEMBLY DOES NOT |
| | MEET THE DESIGN PRESSURES FOR ZONES 2 & 3. |
| | 16-4. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT |
| | RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE |
| | DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE |
| | TO BE DEFFERED. |
| | |
| | |
| | 17-18. OK. |
| | |
| | 19. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN |
| | ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED, SEALED, DATED ORIGINALS. |
| | 19-3. ONLY PAGE A101 IS SIGNED/SEALED BY ARCHITECT. |
| | 19-4. ONLY ONE SET OF ARCHITECTURAL DRAWINGS PROVIDED. |
| | ALL OTHER PLAN SHEETS ARE SIGNED AND SEALED. PROVIDE |
| | SECOND SET OF ARCHITECTURALS, SIGNED AND SEALED. |
| | |
| | |
| | 20-21. OK. |
| | |
| | 22. OK |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED |
| | |
| | |