| Plan Review Notes For Permit 18051235 |
| Permit Number |
18051235 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-25 14:27:17 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO | | | FBC 107.3.5.3(12) | | | | | | 2. THE VALVES FOR THE STACKABLE WASHING MACHINE SHALL | | | BE ACCESSIBLE. PER FBC RES P2903.9.3 | | | | | | 3. THE TANKLESS HEATER SHALL BE MOUNTED A MINIMUM OF 4' | | | FROM ANY OPENINGS IN THE BUILDING. ANSI Z223.1 NFPA 54 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|