| 2018-06-28 17:04:19 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18051235 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. INFO ONLY - [FL. STATUTE 713.13]FILE NOTICE OF |
| | COMMENCEMENT(N.O.C) WITH THE CLERK OF THE COURT AND |
| | PROVIDE CERTIFIED COPY TO WPB BUILDING DEPARTMENT PRIOR |
| | TO SCHEDULING FIRST INSPECTION. THE N.O.C. MUST BE |
| | SIGNED BY THE OWNER.(REQUIRED FOR VALUE OF $2500 AND |
| | ABOVE FOR IMPROVEMENTS TO REAL PROPERTY). |
| | |
| | 2. [FBC R301]PROVIDE 2 COPIES OF SURVEY THAT WILL |
| | INDICATE THE UTILITY EASEMENT ON THE SOUTH SIDE OF |
| | PROPERTY. IF ANY PART OF NEW GARAGE ENCROACHES INTO THE |
| | EASEMENT THEN MOVE GARAGE LOCATION ACCORDINGLY OR |
| | OBTAIN EASEMENT CONSENTS FROM EASEMENT HOLDERS. |
| | |
| | 3. [FBC 107.3.5.3]FINISHED FLOOR ELEVATION NEEDS TO BE |
| | ESTABLISHED. |
| | |
| | 4. [FBC R401.3] PROVIDE DRAINAGE PLAN FOR NEW GARAGE |
| | AND ANY NEW IMPERVIOUS SURFACES TO SHOW COMPLIANCE WITH |
| | R401.3 |
| | USE ESTABLISHED FINISHED FLOOR ELEVATION OF GARAGE AS |
| | BASIS OF DESIGN TO SHOW HOW WATER GETS TO THE STREET |
| | STORM DRAIN. |
| | |
| | 5. [FBC 107.3.5.3]SHEET A203 AT THE BOTTOM OF PAGE IS |
| | LABELED NORTH, BUT IT IS SOUTH ELEVATION. |
| | |
| | 6. [FBC 107.3.5.3]MULTIPLE SHEETS REFER TO SEE |
| | STRUCTURAL SHEET, BUT THERE IS NO STRUCTURAL SHEET. |
| | PLEASE PROVIDE STRUCTURAL AS COMMENTS TO FOLLOW ARE |
| | REQUESTING ADDITIONAL STRUCTURAL INFORMATION. |
| | |
| | 7. [FBC R401.4]PROVIDE DESIGN CRITERIA FOR NEW GARAGE |
| | INCLUDING SOIL REPORT, BEARING CAPACITY, WIND DESIGN |
| | CRITERIA. |
| | |
| | 8. [FBC R301.2.1]PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS. |
| | |
| | 9. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO |
| | BE USED TO MEET REQUIREMNETS OF R703.4 |
| | |
| | 10. [FBC R301.1.2]PROVIDE NOTICE OF APPROVAL(N.O.A.) |
| | FOR ALL WINDOWS, DOORS AND GARAGE DOORS. IF ANY GLAZING |
| | IS NON-IMPACT RATED THEM PROVIDE PROPOSED PROTECTION |
| | AND ATTACHMNET AS OUTLINED IN R301.1.2. |
| | |
| | IF ITEMS PROPOSED ARE NOT KNOWN AT THIS TIME, THEY MAY |
| | BE DEFERRED. |
| | |
| | FBC 107, ALL PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGN PROFESIONAL PRIOR TO SUBMITTAL. |
| | STAMP EACH N.O.A AS REVIEWED, OR PROVIDE ONE REVIEW |
| | SHEET LISTING ALL PRODUCT APPROVALS REVIEWED AND |
| | APPROVED. |
| | |
| | 11. [FBC 107.3.5.3]PROVIDE DETAILS OF HOW NEW OVERHANGS |
| | AND PORCH ARE CONNECTED TO EXISTING AND HOW THEY MEET |
| | WIND LOAD DESIGN CRITERIA. CALL OUT EXISTING STEEL |
| | COLUMNS AND FOOTERS AND DETAIL HOW THEY MEET DESIGN |
| | CRITERIA FOR UPLIFT AND GRAVITY LOADS. IF APPLICABLE |
| | PROVIDE PAD DETAILS AND POST CONNECTIONS. |
| | |
| | 12. [FBC EX807.4]PROVIDE MEANS THAT WERE USED TO |
| | DETERMINE INTERIOR WALLS TO BE DEMOLISHED ARE NON-LOAD |
| | BEARING, AND PROVIDE BACK-UP TO SUPPORT FINDINGS. |
| | |
| | 13. [FBC 107.3.5.3]PROVIDE STRUCTURAL DETAILS OF MAIN |
| | HOUSE INTERIOR CEILING MODIFICATIONS AS INDICATED ON |
| | A103. |
| | |
| | 14. [FBC R602.5]PROVIDE DETAIL OF PROPOSED PARTION AND |
| | INFILL. LIST MATERIALS, SPACING AND CONNECTIONS. |
| | |
| | 15. [FBC 107.3.5.3]PROVIDE ROOF PLAN FOR NEW GARAGE TO |
| | ROOF SLOPE AND SCUPPER LOCATIONS. THE DETAIL ON SHEET |
| | A501 SHOULD COMPLIMENT THE ROOF PLAN. LABLE CONNECTORS |
| | TO BE USED IN DETAILS AND SECTIONS PROVIDED. |
| | |
| | 16. [FBC 107.2.1]PROVIDE PRODUCT APPROVALS FOR ROOFING |
| | MATERIALS. FOR THE FLAT ROOF, INDICATE ASSEMBLY |
| | PROPOSED AND PROVIDE ENGINEERING IF ASSEMBLY DOES NOT |
| | MEET THE DESIGN PRESSURES FOR ZONES 2 & 3. |
| | |
| | THIS MAY BE DEFERRED UPON REQUEST AND SUBMITTED WITH |
| | THE ROOF PERMIT APPLICATION PRIOR TO INSTALLATION. |
| | |
| | 17. [FBC R308.1]SHOWER ENCLOSURES TO COMPLY WITH SAFETY |
| | GLASS STANDARDS IN FBC R308.1 |
| | |
| | 18. [FBC R702.4.2]PROVIDE TILE BACKER IN SHOWER |
| | COMPARTMENTS THAT COMPLY WITH TABLE R702.4.2. |
| | |
| | 19. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN |
| | ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED, SEALED, DATED ORIGINALS. |
| | |
| | 20. A PORTION OF THE FIRST PAGE WAS CROSSED OFF; ONLY |
| | THE ARCHITECT CAN ALTER THE PLAN, FS481. |
| | |
| | 21. A101 REFERS TO INCORRECT GOVERNING CODE; REVISE TO |
| | FBC 2017 RESIDENTIAL. |
| | |
| | 22. FBC 107, SEPARATE PERMITS ARE REQUIRED; ONE PERMIT |
| | FOR THE MAIN HOUSE, ONE PERMIT FOR THE GARAGE. PROVIDE |
| | VALUE FOR EACH. |
| | |
| | |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS |
| | SUBMITTED. |
| | |
| | |
| | |