| Date |
Text |
| 2018-06-04 15:41:27 | 1ST REVIEW FBC-2017 MECHANICAL |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SCOPE OF WORK FOR THE PROPOSED COMMERCIAL |
| | REMODELING PROJECT, AS SHOWN ON THE SUBMITTED PLANS, |
| | INCLUDES BUILDING, MECHANICAL, ELECTRICAL AND PLUMBING |
| | WORK, AND THEREFORE REQUIRES THAT A FL. LICENSED |
| | GENERAL CONTRACTOR SUBMIT A PERMIT APPLICATION- SECTION |
| | 105 WPB. THE SUBMITTED APPLICATION FROM MR. AIR FOR |
| | MECHANICAL VENTILATION MAY BE A SEPARATE PERMIT OR A |
| | SUB-PERMIT UNDER THE GC'S APPLICATION. |
| | |
| | 2) THE PROPOSED GARAGE EXHAUST SYSTEM MUST EITHER RUN |
| | CONTINOUSLY OR INTERMITTENTLY PER SECTION 404.1. FBC M. |
| | BECAUSE THE PROPOSED SYSTEM IS AUTOMATED TO OPERATE |
| | INTERMITTENTLY USING CO AND NO2 SENSORS, THE EXISTING |
| | FAN MUST ALSO BE CONNECTED TO THE SENSORS AND CANNOT BE |
| | CONTROLLED BY A TIME CLOCK. PLEASE NOTE THAT THE |
| | EXHAUST RATE CAN NEVER GO TO ZERO: THE EXHAUST RATE |
| | MUST EITHER BE THE FULL RATE OF 0.75 CFM PER SQ. FT. OR |
| | 0.05 CFM PER SQ. FT. AS DETERMINED BY THE CO AND NO2 |
| | SENSORS. |
| | |
| | 3) VERIFY THAT ALL ROOMS AND OCCUPANCIES THAT ARE |
| | ADJACENT OR ACCESSORY TO THE GARAGE WILL BE MAINTAINED |
| | AT A POSITIVE PRESSURE AND WILL BE PROVIDED WITH |
| | VENTILATION IN ACCORDANCE WITH SECTION 403.3.1 FBC M. |
| | |
| | 4) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE ROOF TOP FAN- SECTION 301.15 FBC M |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |