| 2018-07-07 16:59:35 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. BUILDING'S EXISTING CONDITIONS ARE NOT CLEAR; |
| | THEREFORE COMPLIANCE CANNOT BE DETERMINED. |
| | |
| | A1.0 STATES THAT THE BUILDING IS 20,000 SF, TYPE V |
| | CONSTRUCTION. AERIALS SHOW THAT THIS IS A CONDO UNIT |
| | LOCATED IN A BUILDING WHICH IS APPROXIMATELY 60,000 SF. |
| | REVISE PLAN TO SHOW COMPLIANCE. OUR RECORDS SHOW THIS |
| | BUILDING AS 2 STORY, TYPE IIA CONSTRUCTION. |
| | |
| | A1.0 ALSO STATES THAT THIS WILL BE NON SEPARATED USE. |
| | AT TIME OF CITY SOCCER AND OTHER PERMITTING, COMPLIANCE |
| | WAS SHOWN THAT THE STRUCTURE MET THE REQUIREMENTS OF |
| | BUILDING HEIGHT AND AREA ONLY WITH SEPARTED USE. DUE TO |
| | THE SIZE OF THE BUILDING, SEPARATION IS REQUIRED. |
| | |
| | IF YOU WISH TO HAVE A NON SEPARATED USE, PLEASE DO A |
| | RECORDS RESEARCH REQUEST TO OBTAIN THE CALCULATIONS |
| | DONE IN THE PAST; NON SEPARATED USE WOULD NEED TO TAKE |
| | THAT INFORMATION INTO ACCOUNT. |
| | |
| | OR, PROVIDE EVIDENCE OF A FIRE WALL SEPARATING THE |
| | STRUCTURE INTO SEPARATE BUILDINGS. PRIOR TO |
| | RESUBMITTAL, SEND A DETAIL OF THE FIRE WALL, ALONG WITH |
| | A PLAN SHOWING LOCATION, VIA EMAIL FOR PRELIMINARY |
| | REVIEW. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. |
| | |
| | 2. IS THIS A CHANGE OF OCCUPANCY? REVISE PLAN TO |
| | INCLUDE PREVIOUS OCCUPANCY OF THIS SPACE. IF THIS IS A |
| | CHANGE OF OCCUPANCY, THE REQUIREMENTS OF FBC EB CHAPTER |
| | 10 ARE APPLICABLE; REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 3. SITE LOCATION PLAN DOES NOT APPEAR TO SHOW THE |
| | LOCATION OF THE SPACE, PLEASE REVISE TO CLARIFY, FBC |
| | 107. |
| | |
| | 4. PROVIDE ADDITIONAL INFORMATION ABOUT THE TRAINING |
| | BAYS; WHAT TRAINING OCCURS? THE PLAN SHOWS THIS AREA |
| | EXITING THROUGH THE PROPOSED GARAGE. REVISE PLAN TO |
| | SHOW COMPLIANCE WITH FBC B 1016.2. |
| | |
| | 5. FBC B 1004, PROVIDE OCCUPANT LOAD. OCCUPANT LOAD IS |
| | STATED AS 407; DOOR SHOWS A CAPACITY OF 170. NOTE THAT |
| | ONE EXIT IS NOT SUFFICIENT FOR EITHER, BUT ONLY ONE |
| | PROVIDED. REVISE PLAN TO SHOW SF AREA OF THE "EXISTING |
| | TRAINING", SF AREA OF "PROPOSED GARAGE AREA", OCCUPANT |
| | LOAD FOR EACH. |
| | |
| | |