| 2018-05-29 15:36:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE ARE TWO ELECTRONIC DOOR STRIKES LOCATED IN TWO |
| | SEPARATE STAIRWELLS. |
| | |
| | THESE STAIRWELLS ARE RATED AND NO EQUIPMENT IS TO BE |
| | LOCATED IN THESE STAIRWELLS UNLESS IT IS RELATED TO |
| | FUNCTION OF THE STAIRWELL. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT |
| | SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| | |
| | 7.1.3.2 EXITS. |
| | |
| | (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| | ENCLOSURE |
| | ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING: |
| | (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9) |
| | (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE |
| | (C) REQUIRED EXIT DOOR OPENINGS |
| | (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT |
| | STAIR PRESSURIZATION |
| | (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR |
| | COOLING OF THE EXIT ENCLOSURE |
| | (F) SPRINKLER PIPING |
| | (G) STANDPIPES |
| | (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH |
| | 8.3.5 |
| | (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE |
| | CIRCUITS |
| | ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE |
| | PROTECTED IN ACCORDANCE WITH 8.3.5 |
| | |
| | |
| | THERE IS NO INDICATIONS IN THE CODE FOR THIS EQUIPMENT. |
| | |
| | |
| | PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES |
| | AND NARRATIVE. |
| | |
| | |
| | |
| | 2) ADDITIONALLY TO #1 ABOVE, THERE ARE NO INDICATIONS |
| | OF EXIT RE-ENTRY ON THIS FLOOR OR ANY OTHER FLOOR WHERE |
| | THIS MAY BE ALLOWED. |
| | |
| | PER NFPA 1 & 101 |
| | |
| | 14.5.2.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE |
| | SERVING MORE THAN |
| | FOUR STORIES, UNLESS PERMITTED BY 14.5.2.8.2, SHALL |
| | MEET ONE OF THE |
| | FOLLOWING CONDITIONS: |
| | (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR |
| | OF THE BUILDING |
| | SHALL BE PROVIDED. |
| | (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE |
| | INITIATION OF THE |
| | BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO UNLOCK |
| | ALL STAIR |
| | ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY. |
| | (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE |
| | WITH |
| | 14.5.2.8.1. |
| | [101:7.2.1.5.8] |
| | |
| | PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES |
| | AND NARRATIVE. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |