Plan Review Notes
Plan Review Notes For Permit 18051215
Permit Number 18051215
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-08 11:08:15BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. WORK DESCRIPTION ON APPLICATION CHANGED TO REPLACE
 EXISTING FIRE ESCAPE TO REFLECT SOW ON PLANS.
  
 2. ALL LANDINGS WITHIN STAIR RUNS AND DISCHARGE SHALL
 COMPLY WITH R311.7.6.
 R311.7.6 LANDINGS FOR STAIRWAYS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE MINIMUM WIDTH PERPENDICULAR TO
 THE DIRECTION OF TRAVEL SHALL BE NO LESS THAN THE WIDTH
 OF THE FLIGHT SERVED. LANDINGS OF SHAPES OTHER THAN
 SQUARE OR RECTANGULAR SHALL BE PERMITTED PROVIDED THE
 DEPTH AT THE WALK LINE AND THE TOTAL AREA IS NOT LESS
 THAN THAT OF A QUARTER CIRCLE WITH A RADIUS EQUAL TO
 THE REQUIRED LANDING WIDTH. WHERE THE STAIRWAY HAS A
 STRAIGHT RUN, THE MINIMUM DEPTH IN THE DIRECTION OF
 TRAVEL SHALL BE NOT LESS THAN 36 INCHES (914 MM).
  
 3. ALL GLAZING ALONG THE EXIT PATH OF TRAVEL SHALL BE
 PROTECTED PER FBC EXISTING 405.5.
 405.5 OPENING PROTECTIVES.
 DOORS AND WINDOWS ALONG THE FIRE ESCAPE SHALL BE
 PROTECTED WITH 3/4-HOUR OPENING PROTECTIVES
  
 4. PROVIDE SHOP DRAWINGS OF PROPOSED FIRE ESCAPE.
 DRAWINGS SHALL BE REVIEWED BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 5. PROVIDE CERTIFICATION OF WELDERS FOR ANY ON-SITE
 WELDING.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 6. PROVIDE ENGINEERING EVALUATION REPORT FOR THE
 PROPOSED HELICAL PILES. DESIGNER TO REVIEW AND APPROVE
 PRIOR TO SUBMITTAL.
 R301.1APPLICATION.
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW
 LOADS, WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY
 THIS CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. BUILDINGS
 AND STRUCTURES CONSTRUCTED AS PRESCRIBED BY THIS CODE
 ARE DEEMED TO COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION.
  
 7. STAIR RISERS AND TREADS SHALL COMPLY WITH R311.7.5.1
 & R311.7.5.2.
 R311.7.5.1 RISERS.
 THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (196 MM).
 THE RISER SHALL BE MEASURED VERTICALLY BETWEEN LEADING
 EDGES OF THE ADJACENT TREADS. THE GREATEST RISER HEIGHT
 WITHIN ANY FLIGHT OF STAIRS SHALL NOT EXCEED THE
 SMALLEST BY MORE THAN 3/8 INCH (9.5 MM). RISERS SHALL
 BE VERTICAL OR SLOPED FROM THE UNDERSIDE OF THE NOSING
 OF THE TREAD ABOVE AT AN ANGLE NOT MORE THAN 30 DEGREES
 (0.51 RAD) FROM THE VERTICAL. OPEN RISERS ARE PERMITTED
 PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT
 PERMIT THE PASSAGE OF A 4-INCH-DIAMETER (102 MM)
 SPHERE.
 R311.7.5.2 TREADS.
 THE MINIMUM TREAD DEPTH SHALL BE 10 INCHES (254 MM).
 THE TREAD DEPTH SHALL BE MEASURED HORIZONTALLY BETWEEN
 THE VERTICAL PLANES OF THE FOREMOST PROJECTION OF
 ADJACENT TREADS AND AT A RIGHT ANGLE TO THE TREAD?S
 LEADING EDGE. THE GREATEST TREAD DEPTH WITHIN ANY
 FLIGHT OF STAIRS SHALL NOT EXCEED THE SMALLEST BY MORE
 THAN 3/8 INCH (9.5 MM).
  
 8. GUARDS SHALLL COMPLY WITH R312.1.2.
 R312.1.2 HEIGHT.
 REQUIRED GUARDS AT OPEN-SIDED WALKING SURFACES,
 INCLUDING STAIRS, PORCHES, BALCONIES OR LANDINGS, SHALL
 BE NOT LESS THAN 36 INCHES (914 MM) HIGH MEASURED
 VERTICALLY ABOVE THE ADJACENT WALKING SURFACE, ADJACENT
 FIXED SEATING OR THE LINE CONNECTING THE LEADING EDGES
 OF THE TREADS.
  
 9. APPLICANT TO PRESENT EVIDENCE WHY THEY ARE NOT
 REQUIRED TO COMPLY WITH FBC EXISTING SECTION 405.1.3
 AND PROVIDE EXTERIOR STAIRWAYS IN LIEU OF REPLACING THE
 EXISTING FIRE ESCAPE.
 405.1.3 NEW FIRE ESCAPES.
 NEW FIRE ESCAPES FOR EXISTING BUILDINGS SHALL BE
 PERMITTED ONLY WHERE EXTERIOR STAIRWAYS CANNOT BE
 UTILIZED DUE TO LOT LINES LIMITING STAIRWAY SIZE OR DUE
 TO THE SIDEWALKS, ALLEYS OR ROADS AT GRADE LEVEL. NEW
 FIRE ESCAPES SHALL NOT INCORPORATE LADDERS OR ACCESS BY
 WINDOWS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  