Plan Review Notes
Plan Review Notes For Permit 18051199
Permit Number 18051199
Review Stop P
Sequence Number 2
Notes
Date Text
2018-07-10 13:16:001) THE TDH CALCULATIONS AND THE PUMP CURVE ARE BARELY
 LEGIBLE ON PAGE 4. THE PUMP MODELS ARE ILLLEGIBLE.
 SUBMIT A LEGIBLE POOL PUMP CURVE FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) THE CALCULATIONS SHOW A TDH OF 47.90 FT. TDH. THE
 TDH OF THE PUMP CURVE FOR THE PUMP TO BE INSTALLED
 APEARS TO SHOW THE PUMP CURVE STARTING AT 20 TDH.PLEASE
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW