| Plan Review Notes For Permit 18051185 |
| Permit Number |
18051185 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-31 16:30:00 | 05/31/2018 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) PROVIDE A LEGIBLE PLAN.ADDRESS APPREARS TO HAVE BEEN | | | CUT OFF, PROVIDE FULL ADDRESS ON PLAN. UNABLE TO READ | | | UPPER RIGHT OF PLAN TEXT.FBC 107.2. | | | | | | 2) PROVIDE PIPE SIZING OF ALL SECTIONS OF PIPING. FBC | | | 107.2.1 | | | | | | 3) PROVIDE/ SHOW RAIN SENSOR TO COMPLY WITH FS373.82 | | | | | | 4) VALUE SEEMS TOO LOW. VALUE MUST INCLUDE ALL PARTS, | | | LABOR OVERHEAD, AND PROFIT. WPB AMEND TO THE FBC 109.3 | | | | | | 5) SHOW BACKFLOW DEVICE AND CONNECTION ONTO THE CITY | | | SYSTEM. ALL BACKFLOWS WILL REQUIRED SEPERATE PERMITS | | | AND ALL DEVICES MUST BE LEAD FREE AND STAMP SO ON THE | | | DEVICE. FBC 107.2.1 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] |
|