2018-05-31 16:30:0005/31/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE A LEGIBLE PLAN.ADDRESS APPREARS TO HAVE BEEN
 CUT OFF, PROVIDE FULL ADDRESS ON PLAN. UNABLE TO READ
 UPPER RIGHT OF PLAN TEXT.FBC 107.2.
  
 2) PROVIDE PIPE SIZING OF ALL SECTIONS OF PIPING. FBC
 107.2.1
  
 3) PROVIDE/ SHOW RAIN SENSOR TO COMPLY WITH FS373.82
  
 4) VALUE SEEMS TOO LOW. VALUE MUST INCLUDE ALL PARTS,
 LABOR OVERHEAD, AND PROFIT. WPB AMEND TO THE FBC 109.3
  
 5) SHOW BACKFLOW DEVICE AND CONNECTION ONTO THE CITY
 SYSTEM. ALL BACKFLOWS WILL REQUIRED SEPERATE PERMITS
 AND ALL DEVICES MUST BE LEAD FREE AND STAMP SO ON THE
 DEVICE. FBC 107.2.1
  