Plan Review Notes
Plan Review Notes For Permit 18051174
Permit Number 18051174
Review Stop P
Sequence Number 3
Notes
Date Text
2018-10-16 16:08:443RD REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
  
 1. RE: PLAN SHEET P3; SANITARY ISOMETRIC
 A. KITCHEN 224 SINK: PROVIDE AIR ADMITTANCE VALVE
 CONNECTING ABOVE THE TRAP WEIR OF THE FIXTURE PER FBC
 RES SECTION P3114.
 B. RED LINED ON THE PLAN TO CLARIFY.
 2. RE: PLAN SHEET P3; PLUMBING NOTES
 A. NOTE 11 REGARDING AC CONDENSATE SYSTEM(S); SEE M.2
 MECHANICAL PLAN FOR SIZE AND ROUTING. INSULATE IN
 INTERIOR SPACES.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  