Plan Review Notes
Plan Review Notes For Permit 18051174
Permit Number 18051174
Review Stop E
Sequence Number 3
Notes
Date Text
2018-08-30 09:08:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. RISER SHOWS A METER CAN FEEDING A MLO PANEL (PANEL
 A) AND THE GENERATOR TRANSFER SWITCH (MUST BE SERVICE
 RATED. FIRST FLOOR PLAN SHOWS A METER WITH A MAIN
 DISCONNECT ON CORNER OF GARAGE WITH THE PANELS AND
 TRANSFER SWITCH INSIDE. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 215.5; WPB FBC 107.2.1 (PLAN SHOWS A
 METER CAN WITH A CT CAN, WHICH IS NOT TYPICAL IN A
 RESIDENTIAL INSTALLATION. PERHAPS THIS IS A TRANSFER
 SWITCH, SINCE IT SHOWS A CONDUIT FROM THE GENERATOR?
 THE GENERATOR WOULD NOT TIE IN TO A CT CAN. FURTHER
 CLARIFICATION AND/OR CORRECTION NEEDED FOR RISER. FROM
 METER CAN TO FIRST MEANS OF DISCONNECT, THERE WOULD NOT
 BE AN EQUIPMENT GROUNDING CONDUCTOR (EGC). AFTER THE
 FIRST MEANS, THERE SHOULD BE AN EGC IN EACH CONDUIT.)
 6. IF METER FEEDS DIRECTLY TO PANEL A, THIS PANEL IS
 REQUIRED TO HAVE A MAIN BREAKER. PROVIDE CORRECTION.
 PROVIDE INDICATION THAT TRANSFER SWITCH IS SERVICE
 RATED. NEC 110.3, 230.70; FBC RE E3601.6 (COMMENT IS
 RELATED TO COMMENT 5, WITH FURTHER CORRECTION THIS WILL
 PROBABLY BE ADDRESSED.)
 7. CORRECTED.
 8.CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. WITH THE EXCEPTION OF THE CABANA BATH, PLAN DOES
 NOT SHOW THE 20 AMP CIRCUIT REQUIRED FOR BATHROOM
 RECEPTACLE OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 (POSSIBLY CIRCUITS 18 AND 20 IN PANEL A?, BUT THIS IS
 NOT SHOWN AS BATHROOM GFCI.)
 13. CLOSET LIGHTS ARE SHOWS AS STANDARD RECESS LIGHTS
 OR A CHANDELIER J-BOX. PER CODE: LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 (THESE
 LIGHTS ARE STILL SHOWN AS STANDARD RECESS LIGHTS, AND
 SOME ARE SHOWN DIRECTLY OVER THE STORAGE SPACE, WHICH
 IS A VIOLATION FOR MOST TYPES OF LIGHTS. CORRECTION IS
 NEEDED.)
 14. CORRECTED.
 15. CORRECTED.
 16. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. PROVIDE SMOKE
 ALARM ON EACH STORY OF THE DWELLING. SMOKE ALARMS MUST
 BE INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1; NFPA 72:29.8.3.4 (SYMBOL USED IS NOT IN LEGEND
 AND APPEARS TO BE A SMOKE ALARM ONLY, AS IT DOES NOT
 HAVE AN "SD" INSIDE THE SYMBOL. A CARBON MONOXIDE ALARM
 IS REQUIRED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES. PROVIDE CORRECTION.)
 17. PROVIDE GFCI PROTECTED RECEPTACLE ON BALCONIES. NEC
 210.52(E); FBC RE E3901.7 (BALCONIES THAT CAN BE
 ACCESSED FROM THE INTERIOR OF THE HOME, EVEN IF YOU
 CAN'T WALK OUT ONTO THE BALCONY, MUST HAVE A RECEPTACLE
 OUTLET. THE WEST ELEVATION IS MISSING THIS. PROVIDE
 CORRECTION.)
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. PROVIDE AIC RATING OF SERVICE DISCONNECT, TRANSFER
 SWITCH, AND PANELS. NEC 110.3, 110.9 (NOT SHOWN ON
 PANEL SCHEDULES, MUST BE RATED TO MEET OR EXCEED AIC
 CALCULATION PROVIDED.)
 24. CORRECTED.
  
 NEW COMMENT:
  
 25. NOW THAT THE ROOMS ARE IDENTIFIED ON THE PLAN, I
 SEE THERE IS A STORAGE AREA (ROOM 103) AND A WORKSHOP
 (ROOM 119). THESE AREAS SHOULD HAVE GFCI PROTECTED
 OUTLETS. NEC 210.8(A)(2); FBC RE E3902.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  