| 2018-09-11 12:31:32 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18051174 |
| | PLUMBING COMMENTS: |
| | |
| | 1. RE: PLAN SHEET P3; |
| | A. SHOW TRAP ON ALL UNDERFLOOR FIXTURE DRAINS, IE. |
| | BATHTUBS AND SHOWERS, UNLESS FIXTURE IS INTEGRALLY |
| | TRAPPED, IE. WATER CLOSETS. FBC WPB AMEND 107.2.1, FBC |
| | RES P3201.2 |
| | B. OVAL SYMBOLS AT END OF HORIZONTAL PIPING FOR WATER |
| | CLOSETS AND DISHWASHERS ARE CONFUSING. PROVIDE VERTICAL |
| | EXTENSION AT END OF WATER CLOSET HORIZONTAL AND PLACE |
| | OVAL SYMBOL AT TOP PER FBC WPB AMEND 107.2.1. |
| | DISHWASHER IS TO CONNECT TO SINK TAILPIECE ABOVE TRAP, |
| | NOT DOWNSTREAM OF TRAP PER FBC RES P2717.2 |
| | C. IDENTIFY ALL FIXTURES ON SANITARY ISOMETRIC. |
| | D. SIZE ALL VENTS, FIXTURE DRAINS, FIXTURE BRANCHES, |
| | STACKS, BUILDING DRAIN AND BRANCHES OF THE BUILDING |
| | DRAIN. FBC WPB AMEND 107.2.1 |
| | 2. RE: PLAN SHEET P3; PLUMBING NOTES |
| | A. NOTE 1; CHANGE THE WORDS "ALL APPLICABLE CODES" TO |
| | "THE 2017 FBC RESIDENTIAL CODE AND CITY OF WEST PALM |
| | BEACH AMENDMENTS TO 2017 FBC". FBC WPB AMEND 107.2.1 |
| | B. NOTE 11 REQUIRES PLUMBING CONTRACTOR TO PROVIDE |
| | COMPLETE CONDENSATION SYSTEM. PROVIDE PIPING LAYOUT ON |
| | FLOOR PLAN AND PIPING RISER DIAGRAM TO INCLUDE SIZING |
| | AND DISPOSITION OF CLEAR WASTE. PROVIDE TRAP DETAIL AND |
| | TERMINAL DETAIL, IE. DRYWELL. PROVIDE SPEC FOR |
| | INSULATION IN THE INDOOR SPACES. FBC WPB AMEND 107.2.1 |
| | C. NOTE 14: THE USE OF AIR CHAMBERS IS NOT AN |
| | ACCEPTABLE METHOD FOR PREVENTION OF WATER HAMMER; |
| | PROVIDE WATER HAMMER ARRESTORS IN ACCORDANCE WITH |
| | MANUFACTURER'S INSTRUCTIONS. FBC RES P903.5 |
| | D. ADD NOTE: SHOWER CONTROL VALVE(S) SHALL BE PRESSURE |
| | BALANCED PB,THERMOSTATIC MIXING (TM) OR COMBINATION |
| | PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP. |
| | 2017 FBC RES 2708.4 |
| | E. ADD NOTE: AN ACCESSIBLE TEMPERATURE LIMITING DEVICE |
| | REQUIRED ON HOT WATER TO BATHTUB VALVE(S) IS REQUIRED. |
| | 2017 FBC RES 2713.3 |
| | 3. GROUND FLOOR WASHING MACHINE |
| | A. P3 SANITARY ISOMETRIC: PROVIDE AAV OR AN INDIVIDUAL |
| | VENT WASHING MACHINE FIXTURE DRAIN WHICH MAY REVENT TO |
| | HALF BATH VENT STACK ABOVE FLOOD LEVEL RIM OF THE |
| | FIXTURES. FBC RES P3101.2.1 |
| | B. P1 FLOOR PLAN: THE WASHING MACHINE ON THE FIRST |
| | FLOOR SHALL CONNECT DOWN STREAM OF THE HALF BATHROOM |
| | GROUP. PER FBC RES P3108.1. COORDINATE WITH SANITARY |
| | ISOMETRIC ON P3. |
| | 4. BATH(S)209/210: |
| | A. P3 SANITARY ISOMETRIC; URINAL IS A WALL DISCHARGE |
| | FIXTURE. IT CANNOT CONNECT HORIZONTALLY TO HORIZONTAL |
| | FIXTURE BRANCH. PROVIDE AAV OR AN INDIVIDUAL VENT ABOVE |
| | VERTICAL WASTE PIPE WHICH MAY REVENT TO BATH VENT STACK |
| | ABOVE FLOOD LEVEL RIM OF THE FIXTURES. FBC RES |
| | P3101.2.1 |
| | B. P1 SECOND FLOOR PLAN IS CONFUSING. HORIZONTAL |
| | DRAINAGE BRANCH TO 210 BT AND SHOWER IS NOT SHOWN; |
| | HORIZONTAL PIPING FOR 209/210 DOES NOT MATCH ISOMETRIC |
| | ON P3. FBC WPB AMEND 107.2.1 |
| | 5. BATH 228 |
| | A. P3: A FIXTURE IS MISSING ON SANITARY ISOMETRIC. |
| | PLEASE CLARIFY. FBC WPB AMEND 107.2.1 |
| | B. P1: BATHTUB AND WATER CLOSET FIXTURE DRAINS SHOWN |
| | CONNECTING TO EACH OTHER BEFORE CONNECTING TO(WET)VENT. |
| | MUST CONNECT INDEPENDENTLY TO VENT FBC RES 3108.1; |
| | FIXTURE DRAIN LENGTH TRAP TO VENT TO BE IN ACCORDANCE |
| | WITH FBC RES TABLE P3105.1. |
| | C. P1 PLAN VIEW PIPING AND P3 SANITARY ISOMETRIC DO NOT |
| | MATCH. PLEASE CLARIFY. |
| | 6. LAUNDRY RM 202: P1 SECOND FLOOR PLAN IS CONFUSING. |
| | HORIZONTAL FIXTURE DRAIN FROM WASHING MACHINE SOIL |
| | STACK TO IS NOT SHOWN; DOES NOT MATCH ISOMETRIC ON P3. |
| | PLEASE CLARIFY. FBC WPB AMEND 107.2.1 |
| | 7. CABANA BATH 123: P1 AND P3; HORIZONTAL FIXTURE DRAIN |
| | FROM OUTDOOR KITCHEN SINK MUST CONNECT DOWNSTREAM FROM |
| | CABANA BATH WET VENT, NOT AT THE JUNCTION. FBC RES |
| | P3108.1 |
| | 8. HER BATH 217: P1 PLAN VIEW PIPING AND P3 SANITARY |
| | ISOMETRIC DO NOT MATCH. HORIZONTAL PIPING FROM LAV AND |
| | SHOWER TO SOIL STACK NOT SHOWN ON P1. PLEASE CLARIFY; |
| | NOTE THAT PIPING IN ACCORDANCE WITH THE DRAINAGE FLOW |
| | SHOWN ON P3 MEETS THE REQUIREMENTS OF |
| | P3108.1(HORIZONTAL WET VENTING)WITHOUT THE NEED OF THE |
| | INDIVIDUAL VENTS SHOWN AT THE WATER CLOSET AND BATHTUB. |
| | 9. HALF BATH RM 120/WORKSHOP 119 SINK: WORKSHOP SINK TO |
| | CONNECT DOWNSTREAM OF HALF BATH. FBC RES P3108.1. SHOW |
| | ON P1 AND P3. FBC WPB AMEND 107.2.1 |
| | 10. KITCHEN 224 SINK: NOTE LOCATION OF WASTE STACK FROM |
| | BELOW AND SHOW ANY UNDERFLOOR HORIZONTAL PIPING |
| | REQUIRED ON SECOND FLOOR PLAN P1. P1 AND P3 TO MATCH. |
| | FBC WPB AMEND 107.2.1 |
| | P1 PLAN VIEW PIPING AND P3 SANITARY ISOMETRIC DO NOT |
| | MATCH. PLEASE CLARIFY. |
| | 11. RE; P2 WATER DISTRIBUTION PLAN. SHOW BRANCH PIPING |
| | IN 1ST FLOOR CEILING TO RISERS TO SECOND FLOOR. PLEASE |
| | SIZE ALL RUNOUTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6715 |