2018-09-11 12:31:322ND REVIEW: FBC 2017 6TH EDITION
 PERMIT 18051174
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET P3;
 A. SHOW TRAP ON ALL UNDERFLOOR FIXTURE DRAINS, IE.
 BATHTUBS AND SHOWERS, UNLESS FIXTURE IS INTEGRALLY
 TRAPPED, IE. WATER CLOSETS. FBC WPB AMEND 107.2.1, FBC
 RES P3201.2
 B. OVAL SYMBOLS AT END OF HORIZONTAL PIPING FOR WATER
 CLOSETS AND DISHWASHERS ARE CONFUSING. PROVIDE VERTICAL
 EXTENSION AT END OF WATER CLOSET HORIZONTAL AND PLACE
 OVAL SYMBOL AT TOP PER FBC WPB AMEND 107.2.1.
 DISHWASHER IS TO CONNECT TO SINK TAILPIECE ABOVE TRAP,
 NOT DOWNSTREAM OF TRAP PER FBC RES P2717.2
 C. IDENTIFY ALL FIXTURES ON SANITARY ISOMETRIC.
 D. SIZE ALL VENTS, FIXTURE DRAINS, FIXTURE BRANCHES,
 STACKS, BUILDING DRAIN AND BRANCHES OF THE BUILDING
 DRAIN. FBC WPB AMEND 107.2.1
 2. RE: PLAN SHEET P3; PLUMBING NOTES
 A. NOTE 1; CHANGE THE WORDS "ALL APPLICABLE CODES" TO
 "THE 2017 FBC RESIDENTIAL CODE AND CITY OF WEST PALM
 BEACH AMENDMENTS TO 2017 FBC". FBC WPB AMEND 107.2.1
 B. NOTE 11 REQUIRES PLUMBING CONTRACTOR TO PROVIDE
 COMPLETE CONDENSATION SYSTEM. PROVIDE PIPING LAYOUT ON
 FLOOR PLAN AND PIPING RISER DIAGRAM TO INCLUDE SIZING
 AND DISPOSITION OF CLEAR WASTE. PROVIDE TRAP DETAIL AND
 TERMINAL DETAIL, IE. DRYWELL. PROVIDE SPEC FOR
 INSULATION IN THE INDOOR SPACES. FBC WPB AMEND 107.2.1
 C. NOTE 14: THE USE OF AIR CHAMBERS IS NOT AN
 ACCEPTABLE METHOD FOR PREVENTION OF WATER HAMMER;
 PROVIDE WATER HAMMER ARRESTORS IN ACCORDANCE WITH
 MANUFACTURER'S INSTRUCTIONS. FBC RES P903.5
 D. ADD NOTE: SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB,THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP.
 2017 FBC RES 2708.4
 E. ADD NOTE: AN ACCESSIBLE TEMPERATURE LIMITING DEVICE
 REQUIRED ON HOT WATER TO BATHTUB VALVE(S) IS REQUIRED.
 2017 FBC RES 2713.3
 3. GROUND FLOOR WASHING MACHINE
 A. P3 SANITARY ISOMETRIC: PROVIDE AAV OR AN INDIVIDUAL
 VENT WASHING MACHINE FIXTURE DRAIN WHICH MAY REVENT TO
 HALF BATH VENT STACK ABOVE FLOOD LEVEL RIM OF THE
 FIXTURES. FBC RES P3101.2.1
 B. P1 FLOOR PLAN: THE WASHING MACHINE ON THE FIRST
 FLOOR SHALL CONNECT DOWN STREAM OF THE HALF BATHROOM
 GROUP. PER FBC RES P3108.1. COORDINATE WITH SANITARY
 ISOMETRIC ON P3.
 4. BATH(S)209/210:
 A. P3 SANITARY ISOMETRIC; URINAL IS A WALL DISCHARGE
 FIXTURE. IT CANNOT CONNECT HORIZONTALLY TO HORIZONTAL
 FIXTURE BRANCH. PROVIDE AAV OR AN INDIVIDUAL VENT ABOVE
 VERTICAL WASTE PIPE WHICH MAY REVENT TO BATH VENT STACK
 ABOVE FLOOD LEVEL RIM OF THE FIXTURES. FBC RES
 P3101.2.1
 B. P1 SECOND FLOOR PLAN IS CONFUSING. HORIZONTAL
 DRAINAGE BRANCH TO 210 BT AND SHOWER IS NOT SHOWN;
 HORIZONTAL PIPING FOR 209/210 DOES NOT MATCH ISOMETRIC
 ON P3. FBC WPB AMEND 107.2.1
 5. BATH 228
 A. P3: A FIXTURE IS MISSING ON SANITARY ISOMETRIC.
 PLEASE CLARIFY. FBC WPB AMEND 107.2.1
 B. P1: BATHTUB AND WATER CLOSET FIXTURE DRAINS SHOWN
 CONNECTING TO EACH OTHER BEFORE CONNECTING TO(WET)VENT.
 MUST CONNECT INDEPENDENTLY TO VENT FBC RES 3108.1;
 FIXTURE DRAIN LENGTH TRAP TO VENT TO BE IN ACCORDANCE
 WITH FBC RES TABLE P3105.1.
 C. P1 PLAN VIEW PIPING AND P3 SANITARY ISOMETRIC DO NOT
 MATCH. PLEASE CLARIFY.
 6. LAUNDRY RM 202: P1 SECOND FLOOR PLAN IS CONFUSING.
 HORIZONTAL FIXTURE DRAIN FROM WASHING MACHINE SOIL
 STACK TO IS NOT SHOWN; DOES NOT MATCH ISOMETRIC ON P3.
 PLEASE CLARIFY. FBC WPB AMEND 107.2.1
 7. CABANA BATH 123: P1 AND P3; HORIZONTAL FIXTURE DRAIN
 FROM OUTDOOR KITCHEN SINK MUST CONNECT DOWNSTREAM FROM
 CABANA BATH WET VENT, NOT AT THE JUNCTION. FBC RES
 P3108.1
 8. HER BATH 217: P1 PLAN VIEW PIPING AND P3 SANITARY
 ISOMETRIC DO NOT MATCH. HORIZONTAL PIPING FROM LAV AND
 SHOWER TO SOIL STACK NOT SHOWN ON P1. PLEASE CLARIFY;
 NOTE THAT PIPING IN ACCORDANCE WITH THE DRAINAGE FLOW
 SHOWN ON P3 MEETS THE REQUIREMENTS OF
 P3108.1(HORIZONTAL WET VENTING)WITHOUT THE NEED OF THE
 INDIVIDUAL VENTS SHOWN AT THE WATER CLOSET AND BATHTUB.
 9. HALF BATH RM 120/WORKSHOP 119 SINK: WORKSHOP SINK TO
 CONNECT DOWNSTREAM OF HALF BATH. FBC RES P3108.1. SHOW
 ON P1 AND P3. FBC WPB AMEND 107.2.1
 10. KITCHEN 224 SINK: NOTE LOCATION OF WASTE STACK FROM
 BELOW AND SHOW ANY UNDERFLOOR HORIZONTAL PIPING
 REQUIRED ON SECOND FLOOR PLAN P1. P1 AND P3 TO MATCH.
 FBC WPB AMEND 107.2.1
 P1 PLAN VIEW PIPING AND P3 SANITARY ISOMETRIC DO NOT
 MATCH. PLEASE CLARIFY.
 11. RE; P2 WATER DISTRIBUTION PLAN. SHOW BRANCH PIPING
 IN 1ST FLOOR CEILING TO RISERS TO SECOND FLOOR. PLEASE
 SIZE ALL RUNOUTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER