| 2018-08-29 09:01:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. LOAD CALCULATION SHOWS 40,434 WATTS HVAC LOAD, BUT |
| | THE PANEL SCHEDULES ONLY SHOW THREE SYSTEMS. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. NEC 215.5, 220; FBC RE |
| | E3602.2; WPB FBC 107.2.1 |
| | 5. RISER SHOWS A METER CAN FEEDING A MLO PANEL (PANEL |
| | A) AND THE GENERATOR TRANSFER SWITCH (MUST BE SERVICE |
| | RATED. FIRST FLOOR PLAN SHOWS A METER WITH A MAIN |
| | DISCONNECT ON CORNER OF GARAGE WITH THE PANELS AND |
| | TRANSFER SWITCH INSIDE. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 215.5; WPB FBC 107.2.1 |
| | 6. IF METER FEEDS DIRECTLY TO PANEL A, THIS PANEL IS |
| | REQUIRED TO HAVE A MAIN BREAKER. PROVIDE CORRECTION. |
| | PROVIDE INDICATION THAT TRANSFER SWITCH IS SERVICE |
| | RATED. NEC 110.3, 230.70; FBC RE E3601.6 |
| | 7. SERVICE CONDUCTORS FROM METER CAN TO PANELS IS SHOWN |
| | AS # 2/0 WIRE TO A 200 AMP PANEL. WIRE SIZES FROM NEC |
| | 310.15(B)(7), OR FBC RE E3603.1, CAN ONLY BE USED WHEN |
| | THE SERVICE CONDUCTOR SUPPLIES 100% OF THE LOAD. SINCE |
| | THIS IS NOT THE CASE, PROVIDE CORRECTED WIRE SIZE FROM |
| | METER CAN TO PANELS, RATED FOR THE 200 AMPS SPECIFIED. |
| | NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1 |
| | 8. PLAN SHOWS AHU?S BEING FED WITH #6 WIRE ON A 60 AMP |
| | BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL |
| | WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION. |
| | NEC 334.80; FBC RE E3705.4.4 |
| | 9. OK |
| | 10. OK |
| | 11. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 12. WITH THE EXCEPTION OF THE CABANA BATH, PLAN DOES |
| | NOT SHOW THE 20 AMP CIRCUIT REQUIRED FOR BATHROOM |
| | RECEPTACLE OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| | 13. CLOSET LIGHTS ARE SHOWS AS STANDARD RECESS LIGHTS |
| | OR A CHANDELIER J-BOX. PER CODE: LIGHTING WITH OPEN OR |
| | PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR |
| | LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. |
| | PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 |
| | 14. OK |
| | 15. OK |
| | 16. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET |
| | OF EACH ROOM USED FOR SLEEPING PURPOSES. PROVIDE SMOKE |
| | ALARM ON EACH STORY OF THE DWELLING. SMOKE ALARMS MUST |
| | BE INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET |
| | FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT. |
| | PROVIDE CORRECTIONS. FBC RE R314.3, R315.1; WPB FBC |
| | 107.2.1; NFPA 72:29.8.3.4 |
| | 17. PROVIDE GFCI PROTECTED RECEPTACLE ON BALCONIES. NEC |
| | 210.52(E); FBC RE E3901.7 |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |