2018-06-20 17:11:391ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. E3 THE WASHING MACHINE ON THE FIRST FLOOR SHALL
 CONNECT DOWN STREAM OF THE HALF BATHROOM GROUP. PER FBC
 RES P3108.4
  
 2. THE KITCHEN SINK IN ROOM 115 SHALL BE VENTED BY AN
 AAV OR THE VENT SHALL RUN UP TO SECOND FLOOR ABOVE
 FLOOD LEVEL RIM OF THE FIXTURES BEFORE REVENTING INTO
 THE VENT STACK. PER FBC RES P3101.2.1
  
 3. THE HALF BATHROOM #120 SHALL BE VENTED SEPARATELY
 FROM THE UPSTAIRS KITCHEN AND CONNECT TO THE HORIZONTAL
 BUILDING DRAIN NOT THE SOIL STACK. PER FBC RES
 P3101.2.1 , P3108.4
  
 4. THE SINK IN THE WORK SHOP SHALL CONNECT TO THE
 BUILDING DRAIN DOWN STREAM OF THE HALF BATHROOM.
 P3108.4
  
 5. PLEASE PROVIDE PLUMBING FLOOR PLAN INCLUDING WATER
 AND SANITARY TO DETERMINE CODE COMPLIANCE OF PLUMBING
 SYSTEM DESIGN. PER WPB AMEND TO FBC 107.2.1
  
 6. UNDER WORK DESCRIPTION ON PERMIT APPLICATION IT
 STATES A 14X 35 FIBERGLASS POOL PROVIDE PLANS OR REMOVE
 FROM WORK DESCRIPTION. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  