| 2018-06-29 10:42:11 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18051174 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 110.9] DETAIL 4-A9 WAS PROVIDED (SITE WALL). I |
| | WAS UNABLE TO LOCATE PROPOSED LOCATION (C1, A1), PLEASE |
| | ADVISE WHERE THIS CAN BE FOUND OR ADD TO PLAN. IF IT IS |
| | NEAR THE PROPERTY LINE, SHOW LOCATION OF FOOTING |
| | RELATIVE TO THE PROPERTY LINE. TYPICALLY AN ECCENTRIC |
| | FOOTER IS REQUIRED FOR SITE WALL. |
| | |
| | IF A SITE (RETAINING) WALL IS NOT PROPOSED, REVISE C1 |
| | TO SHOW PROPOSED GRADES AND GRADES ON ADJACENT PARCEL |
| | TO SHOW HOW WATER WILL BE DIRECTED TO DRAIN TO STORM |
| | DRAIN AT FRONT OF PROPERTY OR SWALE TO THE REAR RATHER |
| | THAN ADJACENT PARCEL. |
| | |
| | 2.[FBC R401.3]SITE DRAINAGE TO PROVIDE 2% SLOPE FOR |
| | IMPERVIOUS SURFACES WITHIN 10' OF THE FOUNDATION. |
| | |
| | 3.[FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING |
| | CAPACITY AS REFERENCED ON SHEET S4. |
| | |
| | 4.[FBC 107] PROVIDE CUT SHEET FOR ICYNENE WITH THE TYPE |
| | SELECTED TO ESTABLISH THICKNESS NEEDED TO MEET REQUIRED |
| | R-VALUE. |
| | |
| | 5.[FBC R302.9.1 & R302.9.2]ADD NOTE TO SHEET A9 THAT |
| | FINISHES SHALL HAVE A FLAME SPEAD INDEX OF NOT GREATER |
| | THAN 200 AND SMOKE DEVELOPED INDEX OF NOT GREATER THAN |
| | 400. |
| | |
| | 6.[FBC R506.2.3]S-1 SHOWS CORRECT VAPOR BARRIER, BUT |
| | SHEET A9 SHOWS CONFLICTING NUMBERS. PLEASE ADJUST SHEET |
| | A-9 TO MATCH SHEET S-1. |
| | |
| | 7.[FBC R506.2.4] ADD NOTE ON SHEET S1 FOR CONTRACTION |
| | JOINTS TO COMPLY WITH ACI 332 OR APPROVED INDUSTRY |
| | STANDARD. |
| | |
| | 8.[R302.6]NOTE ON A-2 CALLS OUT TYPE X DRYWALL ON |
| | CEILING IN GARAGE. TO AVOID FIELD/INSPECTION ISSUES, IT |
| | IS SUGGESTED TO CALL OUT TYPE X DRYWALL ON SECTION 1/A9 |
| | TO MATCH. |
| | |
| | 9.[FBC 107.3.5.3]UPDATE SHEET S4 STRUCTURAL NOTES TO |
| | REFERENCE FBC 2017 6TH EDITION IN LINE JUST BELOW CODES |
| | AND STANDARDS. |
| | |
| | 10.[FBC 107.3.5.3]PROVIDE LINTEL SCHEDULE FOR EACH |
| | WINDOW/DOOR WHERE LINTEL IS TO BE PROVIDED. THIS IS TO |
| | ESTABLISH MINIMUM BEARING TO MATCH N.O.A. 17-0821.18. |
| | |
| | 11.[FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO |
| | BE USED TO MEET REQUIREMNETS OF R703.4 |
| | |
| | 12.[FBC R302.11]ADD FIREBLOCKING TO DETAIL SHEET A9 ON |
| | TYPICAL WALL SECTIONS. |
| | |
| | 13.[FBC R407.2]ADD NOTE THAT THAT STATES HOW STEEL |
| | COLUMNS WILL MEET PRTECTION REQUIREMENTS IN R407.2 |
| | |
| | 14.[R302.12]UPDATE DRAFTSTOPPING NOTE ON SHEET A8 TO |
| | SAY R302.12 INSTEAD OF R301.12. ALSO, COPY/PASTE THIS |
| | NOTE TO SHEET S2 WHERE FLOOR TRUSSES ARE ARE SHOWN IN |
| | PLAN VIEW. |
| | |
| | 15.[FBC R311.3 & R311.3.1]EGRESS LANDING SHALL NOT BE |
| | LESS THAN 1 1/2" LOWER THAN THE TOP OF THRESHOLD.SHOW |
| | DIMENSION OF LANDING IN RELATIONSHIP TO FINISHED FLOOR |
| | ON SHEET A8 AND S1. |
| | |
| | 16.[FBC R310]PROVIDE DETAIL OF HOW DECO RAILS AT EGRESS |
| | WINDOWS MEET EGRESS REQUIREMENTS. |
| | |
| | 17.[FBC 107.2.1]PROVIDE NOTICE OF ACCEPTANCE(N.O.A) |
| | THAT IS NOT EXPIRED FOR N.O.A. 17-1212.2A AND N.O.A. |
| | 17-1212.09. |
| | |
| | 18. [FBC 107, FBC R 301] THE SHINGLE PRODUCT APPROVAL |
| | IS OK |
| | FOR THE FLAT DECK, THE ASSEMBLY PROPOSED AND |
| | ENGINEERING FOR ZONES 2 & 3, IF APPLICABLE, IS |
| | REQUIRED. |
| | |
| | ALTERNATIVELY, THIS MAY BE PROVIDED AT TIME OF ROOF SUB |
| | PERMIT APPLICATION UPON REQUEST. |
| | |
| | 19. [FBC 109], A VALUATION ADJUSTMENT HAS BEEN DONE PER |
| | ICC TABLES: |
| | $945,112.55 UNDER AIR (7979 SQ. FT. X 118.45) |
| | $80,065.00 UNDER ROOF (1675 SQ. FT. X 47.80) |
| | 1,025,177.50 TOTAL EVALUATION |
| | |
| | 20. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | A. ENGINEERED TRUSS DRAWINGS REQUIRED AT INSPECTION |
| | B. SEPARATE PERMITS REQUIRED FOR DEMO, FENCING, WALLS |
| | SITE WALLS AND POOL. |
| | C. STAIR ENGINEERING IS TO BE REVIEWED BY DESIGNER OF |
| | RECORD AND SUBMITTED TO BUILDING DIVISION FOR REVIEW |
| | PRIOR TO INSTALLATION. |
| | |