Plan Review Notes
Plan Review Notes For Permit 18051164
Permit Number 18051164
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-14 05:39:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER.FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. DISCONNECT REQUIRED WITHIN SIGHT OF SIGNS. NEC
 600.6A(1)
  
 3. DUE TO THE DISCONNECT REQUIREMENTS OF NEC 600.6A(1)
 AN ELECTRICAL SUB-PERMIT CANNOT BE ISSUED TO A
 CONTRACTOR HOLDING AN ES LICENSE. A CONTRACTOR WITH AN
 ER OR EC LICENSE MUST APPLY FOR THE PERMIT AND PERFORM
 THE NECESSARY WORK. PLEASE SEE SCOPE OF WORK FOR ES
 LICENSE.
  
 F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SIGN
 CONTRACTORS, SPECIALTY ELECTRICAL CONTRACTORS, (#2 SIGN
 SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION
 INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE
 FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR,
 SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE
 LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE
 THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE
 LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A
 CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE
 ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN
 DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE
 INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH
 REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO
 HUNDRED FIFTY (250) VOLTS MAXIMUM.
  
 4. VALUE OF WORK TOO LOW, PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
  