| 2018-06-14 05:39:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER.FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 |
| | |
| | 2. DISCONNECT REQUIRED WITHIN SIGHT OF SIGNS. NEC |
| | 600.6A(1) |
| | |
| | 3. DUE TO THE DISCONNECT REQUIREMENTS OF NEC 600.6A(1) |
| | AN ELECTRICAL SUB-PERMIT CANNOT BE ISSUED TO A |
| | CONTRACTOR HOLDING AN ES LICENSE. A CONTRACTOR WITH AN |
| | ER OR EC LICENSE MUST APPLY FOR THE PERMIT AND PERFORM |
| | THE NECESSARY WORK. PLEASE SEE SCOPE OF WORK FOR ES |
| | LICENSE. |
| | |
| | F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SIGN |
| | CONTRACTORS, SPECIALTY ELECTRICAL CONTRACTORS, (#2 SIGN |
| | SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION |
| | INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE |
| | FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR, |
| | SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE |
| | LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE |
| | THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE |
| | LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A |
| | CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE |
| | ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN |
| | DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE |
| | INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH |
| | REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO |
| | HUNDRED FIFTY (250) VOLTS MAXIMUM. |
| | |
| | 4. VALUE OF WORK TOO LOW, PROVIDE COPY OF SIGNED |
| | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL |
| | MATERIALS AND LABOR. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | |