| 2018-06-11 07:45:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18051156 |
| | 6/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 508.1.1 FBC M AND SHOW COMPLIANCE. |
| | MAKEUP AIR TEMPERATURE. |
| | |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10F (6C) |
| | EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS OF THE |
| | MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC |
| | SYSTEM. |
| | |
| | ADVISORY: IF CHOOSING TO MEET THE EXCEPTION AS STATED |
| | IN THE CODE SECTION ABOVE, AC LOAD CALCULATIONS MUST BE |
| | SUBMITTED THAT INCLUDE THE ADDED HEAT LOAD OF THE |
| | MAKEUP AIR. PLEASE CONTACT CAPTIVEAIRE FOR DATA |
| | INDICATING THE PERCENTAGE OF MAKEUP AIR THAT IS |
| | EXHAUSTED, AND THE PERCENTAGE THAT SPILLS OVER INTO THE |
| | KITCHEN SPACE. |
| | |
| | 2) SUBMIT THE NOA'S FOR THE ROOF FANS- RULE 9N-3 FAC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |