| Plan Review Notes For Permit 18051063 |
| Permit Number |
18051063 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-23 08:48:58 | PASSED WITH PROVISO; NOTIFIED APPLICANT VIA EMAIL | | | | | | THE MULLION IS SCANNED IN REVERSE ORDER. I'VE | | | RE-SCANNED IT AND ATTACHED IT - THE NEW DOCUMENT HAS | | | THE SAME NAME BUT INCLUDES THE FL NUMBER AT THE END. | | | | | | THE WIND PRESSURE DIAGRAM DOESN'T INDICATE MEAN ROOF | | | HEIGHT. YOU CAN WRITE THIS ON YOUR WIND PRESSURE CHART | | | OR FLOOR PLAN RATHER THAN MARKING UP THE ENGINEERING. | | | | | | FOR $250 YOU CAN "MASTER" A WIND LOAD CHART FOR EACH | | | BUILDING; THEN YOU DON'T NEED TO PROVIDE AN ORIGINAL | | | FOR EACH JOB. | | | | | | THE DESIGN PRESSURES DON'T MATCH THE ENGINEERING, SEE | | | BELOW. OPENINGS 1 AND 2 ARE OK, 3 SHOULD BE | | | -65.9/+65.9, 4 SHOULD BE -64.5/+63.6. SINCE SMALLER | | | OPENINGS HAVE HIGHER DESIGN PRESSURES, YOU NEED TO USE | | | THE SMALLER COLUMN. |
|