Plan Review Notes
Plan Review Notes For Permit 18051052
Permit Number 18051052
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-15 11:15:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 2. PROVIDE GFCI PROTECTION FOR RECEPTACLES PER NEC
 210.8
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12.
 4. PLAN SHOWS A CHANDELIER IN BATHROOM. BE ADVISED THAT
 NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-,
 OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS,
 OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED
 WITHIN A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION IF NEEDED, SIZE OF
 CHANDELIER NOT SHOWN. NEC 410.10(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  