| 2018-08-28 07:50:08 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE VENT MAYBE REQUIRED TO BE LARGER THAN 2IN. . |
| | VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE |
| | INCREASED BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE |
| | DEVELOPED LENGTH OF THE VENT PIPE. INDICATE LENGTH OF |
| | ALL CONNECT VENTS ON PLAN. PER FBC PL 906.2 |
| | |
| | 2. THE DRINKING FOUNTAIN IS MISSING FROM THE WATER |
| | ISOMETRIC PLEASE CLARIFY.WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PREVIOUS COMMENT: ON THE SANITARY ISOMETRIC THE |
| | SHOWER IN THE STAFFF BATHROOM IS STILL LABELED AS A |
| | FLOOR DRAIN WITH A TRAP PRIMER PLEASE LABEL ALL FIXTURE |
| | TO MATCH THE FIXTURES THEY SERVE. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. ON THE SANITARY ISOMETRIC PLEASE CORRECT THE |
| | FOLLOWING THE LAVATORY IN THE STAF BATHROOM IS NOT |
| | MARKED, THE BREAKROOM SINK AND THE MOP SINK ARE MARKED |
| | AS A LAVATORY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. ON THE SANITARY ISOMETRIC IN THE STAFF BATHROOM WITH |
| | THE SHOWER THE LAVATORY BRANCH DRAIN SHALL CONNECT |
| | BETWEEN THE TOILET AND SHOWER, TWO FIXTURE ARE NPT |
| | PERMITTED UP STREAM OF THE VENT ON A WET VENT SYSTEM. |
| | PER FBC PL 912.1 |
| | |
| | 6. THE DRINKING FOUNTAIN IS MISSING THE VENT ON THE |
| | ISOMETRIC DRAWING. PLEASE CLARIFY. PER FBC PL 901.2.1 |
| | |
| | 7. ON SHT. A9.0.2 IT APPEARS THAT THE INSIDE CLEAR |
| | DIMENSION OF THE TRANSFER SHOWER IN THE STAFF BATHROOM |
| | IS SHOWING 3'-11/4" IT SHALL BE 36" INSIDE DIMENSION. |
| | FBC ACC 608.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |