| 2018-06-25 15:29:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18051051 |
| | 6/25/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.1: THE O/A CALCULATIONS FOR AHU-1 ARE |
| | INCORRECT ACCORDING TO TABLE 403.3.1.1 FBC M. THE TOTAL |
| | NUMBER OF PEOPLE FOR CONFERENCE ROOMS IS BASED ON 50 |
| | PERSONS PER SQ. FT. PLEASE CORRECT THE CALCULATIONS AND |
| | THE OUTDATED CODE REFERENCE. |
| | |
| | 2) M2.1: PLEASE REVISE NOTE #2 TO INDICATE THE ACCESS |
| | HATCH WILL BE SIZED LARGE ENOUGH TO REMOVE AND REPLACE |
| | THE AIRHANDLER, AND A LEVEL WORKING SPACE NOT LESS THAN |
| | 30 INCHES DEEP AND 30 INCHES WIDE SHALL BE PROVIDED IN |
| | FRONT OF THE CONTROL SIDE OF THE UNIT- SECTION 306.1 |
| | FBC M. |
| | |
| | 3) M2.1: PLEASE PROVIDE A NOTE ON THE PLAN TO INDICATE |
| | THE EXTERIOR CONDENSERS WILL BE INSTALLED TO PROVIDE |
| | WORKING CLEARANCES PER THE MANUFACTURER, AND IN |
| | ACCORDANCE WITH SECTION 306.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |