| Date |
Text |
| 2018-06-08 07:05:46 | THE PLAN HAS BEEN PASSED PROVISIONALLY: FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECT FEE(S) |
| | |
| | 1. PROVIDE PANEL SCHEDULE AND LOAD CALCULATION BY FINAL |
| | INSPECTION. PERMIT REFERENCED BY CONTRACTOR #18040526 |
| | IS A STAND ALONE SERVICE CHANGE PERMIT WITH NO PANEL |
| | SCHEDULE OR LOAD CALCULATION. |
| | |
| | 2. EGRESS LIGHTING REQUIRED AT ALL ENTRANCES/EXIT DOORS |
| | TO THE DWELLING EXECPT THE (VEHICLE DOOR) FOR THE |
| | GARAGE. FOR DWELLING UNITS, ATTACHED GARAGES, AND |
| | DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| | FBC RE E3903.3 |
| | |
| | 3. VALUE HAS BEEN ADJUSTED TO 4500$ THE INCREASED VALUE |
| | OF 1000$ ADDED TO THE INITIAL 2000$ TO MAKE 3000$ TOTAL |
| | IS INSUFFICIENT. |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |