2019-03-15 10:06:51PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) 3RD REQUEST. PROVIDE FULL AND COMPLETE MANUFACTURES
 INSTALLATION SPECIFICATION FOR THE GREASE INTERCEPTOR.
 PROPERLY SIZE INTERCEPTOR EITHER TO CHAPTER 10 OF THE
 PBC PLUMBING CODE OR TO FLORIDA ADMIN CODE (F.A.C)
 64E-6. YOUR SIZING ON SHT P-2 BASED ON TABLE 604.3 IS
 INCORRECT. GPM IS BASED ON WHAT THE 3 COMPARTMENT SINK
 IS ABLE TO DISCHARGE ALL AT ONCE NOT WHAT THE MIN GPM/
 PRESSURE OF A FAUCET IS SUPPOSE TO BY.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703