| 2019-03-15 10:06:51 | PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1) 3RD REQUEST. PROVIDE FULL AND COMPLETE MANUFACTURES |
| | INSTALLATION SPECIFICATION FOR THE GREASE INTERCEPTOR. |
| | PROPERLY SIZE INTERCEPTOR EITHER TO CHAPTER 10 OF THE |
| | PBC PLUMBING CODE OR TO FLORIDA ADMIN CODE (F.A.C) |
| | 64E-6. YOUR SIZING ON SHT P-2 BASED ON TABLE 604.3 IS |
| | INCORRECT. GPM IS BASED ON WHAT THE 3 COMPARTMENT SINK |
| | IS ABLE TO DISCHARGE ALL AT ONCE NOT WHAT THE MIN GPM/ |
| | PRESSURE OF A FAUCET IS SUPPOSE TO BY. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | 561-248-2703 |