| 2019-01-08 11:25:27 | CODES IN EFFECT |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 3RD REVIEW: DENIED |
| | PLUMBING COMMENTS |
| | |
| | 1. THE DIMENSION FROM THE SIDE WALL TO THE CENTER OF |
| | THE TOILET READS 18" MIN WHICH IS NOT CODE COMPLIANT |
| | THE CODE IS 16" MIN - 18" MAX. THIS WAS REVISED AND |
| | CLOUDED ON P-2 BUT MUST ALSO BE CORRECTED ON THE ADA |
| | TOILET DETAIL ON A-1 PER WPB FBC 107.2.1. |
| | 2. 2ND REQUEST: PROVIDE THE MANUFACTURE SPECIFICATIONS |
| | INCLUDING DETAILAND INSTALLATION GUIDE FOR THE GREASE |
| | INTERCEPTOR PER WPB FBC 107.2.1. PLEASE CONTACT JEFF |
| | ODOMS @ 561-822-2172 OR [email protected] AT THE WPB |
| | UTILITIES DEPARTMENT WITH QUESTIONS. |
| | 3. LOOKING AT ALL OF THE PLANS IT IS UNCLEAR WHETHER OR |
| | NOT THE GREASE INTERCEPTOR WILL BE IN AN AREA SUBJECT |
| | TO VEHICULAR TREAFFIC. PLEASE CLARIFY ON THE PLANS PER |
| | WPB FBC 107.2.1, AND IF NECCESARY PROVIDE TRAFFIC |
| | BEARING LID AND INCLUDE IN SPEC/DETAIL PER WPB FBC |
| | 107.2.1. |
| | 3. RE: THREE COMPARTMENT SINK; |
| | A. ON THE SANITARY ISOMETRIC, IDENTIFY THE OPEN |
| | RECEPTACLE (IE. WASTE )PER WPB FPC 107.2.1 AND PROVIDE |
| | A TRAP FOR THE SAME RECEPTACLE PER FBC PL 1002.1. THE |
| | GREASE INTERCEPTOR DOES NOT CONSTITUTE A TRAP FOR |
| | FIXTURES AS LAID OUT IN FBC PL 1002.1 (2). |
| | B. THE DETAIL FOR THE 3 COMPARTMENT SINK SHOWS A FLOOR |
| | DRAIN. CHANGE DESCRIPTION TO WASTE RECEPTACLE TO COMPLY |
| | WITH THE REQUIREMENTS OF FBC PL 802.3. |
| | C. THE DETAIL FOR THE 3 COMPARTMENT SINK SHOWS THE |
| | INDIRECT WASTE TRAPPED. THE TRAP IS NOT REQUIRED AS THE |
| | INDIRECT WASTE CONFORMS TO THE GUIDELINES NOTED IN FBC |
| | PL 802.2. |
| | D. THE DETAIL FOR THE 3 COMPARTMENT SINK DESCRIBES THE |
| | FIXTURE AS "SINK". CHANGE DESCRIPTION TO "SINK |
| | COMPARTMENT" TO COMPLY WITH THE REQUIREMENTS OF FBC PL |
| | 802.1.1 |
| | E. RECONCILE THE THREE COMPARTMENT SINK WASTE PIPE ON |
| | THE ISOMETRIC WITH THE DETAIL FOR THE 3 COMP. SINK |
| | INDIRECT WASTE PER WPB FBC 107.2.1. |
| | 4. RE: 4" TWO WAY CLEANOUT FOR THE REQUIRED SAMPLING |
| | POINT FOR GREASE INTERCEPTOR; |
| | A. ON THE SANITARY ISOMETRIC, SIZE THE GREASE |
| | INTERCETOR EFFLUENT PIPING 4" TO ACCOMMODATE THE 4" TWO |
| | WAY CLEANOUT PROVIDED AS A SAMPLING POINT PER FBC PL |
| | 704.2 AND 706.2. |
| | B. REMOVE THE WORDS "WITH CAP ON BOTTOM &" FROM THE |
| | SAMPLING POINT NOTES PER WPB FBC 107.2.1. |
| | 5. RE: WATER FOUNTAIN; |
| | A. ADD THE WATER FOUNTAIN TO THE FIXTURE SCHEDULE |
| | NOTING COMPLIANCE WITH FBC ACC SECTIONS 211 AND 602 PER |
| | WPB FBC 107.2.1. |
| | B. SHOW THE WATER FOUNTAIN ON THE A-3 PROPOSED FLOOR |
| | PLAN NOTING COMPLIANCE WITH FBC ACC SECTIONS 211 AND |
| | 602 PER WPB FBC 107.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |