Plan Review Notes
Plan Review Notes For Permit 18050987
Permit Number 18050987
Review Stop P
Sequence Number 3
Notes
Date Text
2019-01-08 11:25:27CODES IN EFFECT
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW: DENIED
 PLUMBING COMMENTS
  
 1. THE DIMENSION FROM THE SIDE WALL TO THE CENTER OF
 THE TOILET READS 18" MIN WHICH IS NOT CODE COMPLIANT
 THE CODE IS 16" MIN - 18" MAX. THIS WAS REVISED AND
 CLOUDED ON P-2 BUT MUST ALSO BE CORRECTED ON THE ADA
 TOILET DETAIL ON A-1 PER WPB FBC 107.2.1.
 2. 2ND REQUEST: PROVIDE THE MANUFACTURE SPECIFICATIONS
 INCLUDING DETAILAND INSTALLATION GUIDE FOR THE GREASE
 INTERCEPTOR PER WPB FBC 107.2.1. PLEASE CONTACT JEFF
 ODOMS @ 561-822-2172 OR [email protected] AT THE WPB
 UTILITIES DEPARTMENT WITH QUESTIONS.
 3. LOOKING AT ALL OF THE PLANS IT IS UNCLEAR WHETHER OR
 NOT THE GREASE INTERCEPTOR WILL BE IN AN AREA SUBJECT
 TO VEHICULAR TREAFFIC. PLEASE CLARIFY ON THE PLANS PER
 WPB FBC 107.2.1, AND IF NECCESARY PROVIDE TRAFFIC
 BEARING LID AND INCLUDE IN SPEC/DETAIL PER WPB FBC
 107.2.1.
 3. RE: THREE COMPARTMENT SINK;
 A. ON THE SANITARY ISOMETRIC, IDENTIFY THE OPEN
 RECEPTACLE (IE. WASTE )PER WPB FPC 107.2.1 AND PROVIDE
 A TRAP FOR THE SAME RECEPTACLE PER FBC PL 1002.1. THE
 GREASE INTERCEPTOR DOES NOT CONSTITUTE A TRAP FOR
 FIXTURES AS LAID OUT IN FBC PL 1002.1 (2).
 B. THE DETAIL FOR THE 3 COMPARTMENT SINK SHOWS A FLOOR
 DRAIN. CHANGE DESCRIPTION TO WASTE RECEPTACLE TO COMPLY
 WITH THE REQUIREMENTS OF FBC PL 802.3.
 C. THE DETAIL FOR THE 3 COMPARTMENT SINK SHOWS THE
 INDIRECT WASTE TRAPPED. THE TRAP IS NOT REQUIRED AS THE
 INDIRECT WASTE CONFORMS TO THE GUIDELINES NOTED IN FBC
 PL 802.2.
 D. THE DETAIL FOR THE 3 COMPARTMENT SINK DESCRIBES THE
 FIXTURE AS "SINK". CHANGE DESCRIPTION TO "SINK
 COMPARTMENT" TO COMPLY WITH THE REQUIREMENTS OF FBC PL
 802.1.1
 E. RECONCILE THE THREE COMPARTMENT SINK WASTE PIPE ON
 THE ISOMETRIC WITH THE DETAIL FOR THE 3 COMP. SINK
 INDIRECT WASTE PER WPB FBC 107.2.1.
 4. RE: 4" TWO WAY CLEANOUT FOR THE REQUIRED SAMPLING
 POINT FOR GREASE INTERCEPTOR;
 A. ON THE SANITARY ISOMETRIC, SIZE THE GREASE
 INTERCETOR EFFLUENT PIPING 4" TO ACCOMMODATE THE 4" TWO
 WAY CLEANOUT PROVIDED AS A SAMPLING POINT PER FBC PL
 704.2 AND 706.2.
 B. REMOVE THE WORDS "WITH CAP ON BOTTOM &" FROM THE
 SAMPLING POINT NOTES PER WPB FBC 107.2.1.
 5. RE: WATER FOUNTAIN;
 A. ADD THE WATER FOUNTAIN TO THE FIXTURE SCHEDULE
 NOTING COMPLIANCE WITH FBC ACC SECTIONS 211 AND 602 PER
 WPB FBC 107.2.1.
 B. SHOW THE WATER FOUNTAIN ON THE A-3 PROPOSED FLOOR
 PLAN NOTING COMPLIANCE WITH FBC ACC SECTIONS 211 AND
 602 PER WPB FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715