| 2018-08-30 11:29:17 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE DIMENSION FROM THE SIDE WALL TO THE CENTER OF |
| | THE TOILET READS 18" MIN WHICH IS NOT CODE COMPLIANT |
| | THE CODE IS 16" MIN - 18" MAX PLEASE CLARIFY ON THE |
| | PLAN. PER FBC ACC 604.2 |
| | |
| | 2. ON THE GREASE INTERCEPTOR SIZING CALCULATION YOU |
| | LISTED A TABLE THAT IS USED FOR SIZING SANITARY PIPING |
| | BY USING DRAINAGE FIXTURE UNITS IT'S CONFUSING BECAUSE |
| | THE CODE USES GALLONS PER-MINUTE IN TABLE FBC PL |
| | 1003.3.4.1 MOST SMALLER GREASE INTERCEPTORS LIKE THIS |
| | ONE USE THE PDI METHOD 8.3.2, THE CALCULATIONS NEED TO |
| | INCLUDE THE GPM OF THE FIXTURE, FLOW THROUGH THE |
| | INTERCEPTOR AND THE GREASE RETENTION OF THE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 AND FBC PL |
| | 1003.2 |
| | |
| | 3. THE 3 COMP SINK SHALL BE INDIRECT DRAINED PER FBC PL |
| | 802.1 THE PLAN SHOWS A DETAIL OF THE INDIRECT WASTE BUT |
| | THE ISOMETRIC SHOW A DIRECT CONNECTION IT SHOULD SHOW |
| | THE FLOOR SINK ON THE HORIZONTAL DRAIN BEING VENTED BY |
| | THE HAND SINK PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4.PROVIDE THE MANUFACTURE SPECIFICATIONS AND |
| | INSTALLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. THE SAMPLING PORT SHALL NOT HAVE SUMP BELOW IT A 4" |
| | TWO WAY CLEAN OUT OR PRE MANUFACTURED SAMPLING PORT |
| | SHALL BE USED. PER WPB UTILITIES DEPT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |