2018-08-30 11:29:172ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DIMENSION FROM THE SIDE WALL TO THE CENTER OF
 THE TOILET READS 18" MIN WHICH IS NOT CODE COMPLIANT
 THE CODE IS 16" MIN - 18" MAX PLEASE CLARIFY ON THE
 PLAN. PER FBC ACC 604.2
  
 2. ON THE GREASE INTERCEPTOR SIZING CALCULATION YOU
 LISTED A TABLE THAT IS USED FOR SIZING SANITARY PIPING
 BY USING DRAINAGE FIXTURE UNITS IT'S CONFUSING BECAUSE
 THE CODE USES GALLONS PER-MINUTE IN TABLE FBC PL
 1003.3.4.1 MOST SMALLER GREASE INTERCEPTORS LIKE THIS
 ONE USE THE PDI METHOD 8.3.2, THE CALCULATIONS NEED TO
 INCLUDE THE GPM OF THE FIXTURE, FLOW THROUGH THE
 INTERCEPTOR AND THE GREASE RETENTION OF THE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 AND FBC PL
 1003.2
  
 3. THE 3 COMP SINK SHALL BE INDIRECT DRAINED PER FBC PL
 802.1 THE PLAN SHOWS A DETAIL OF THE INDIRECT WASTE BUT
 THE ISOMETRIC SHOW A DIRECT CONNECTION IT SHOULD SHOW
 THE FLOOR SINK ON THE HORIZONTAL DRAIN BEING VENTED BY
 THE HAND SINK PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4.PROVIDE THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB
 AMEND TO FBC 107.2.1
  
 5. THE SAMPLING PORT SHALL NOT HAVE SUMP BELOW IT A 4"
 TWO WAY CLEAN OUT OR PRE MANUFACTURED SAMPLING PORT
 SHALL BE USED. PER WPB UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  