| Plan Review Notes For Permit 18050987 |
| Permit Number |
18050987 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-09-02 13:09:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. SEE PLUMBING COMMENTS. | | | | | | 2. FBC A 904, PROVIDE A DETAIL FOR THE SALES COUNTER. | | | | | | OLD SHEETS APPEAR TO HAVE BEEN REMOVED. LOCATION OF | | | SALES COUNTER NOT CLEAR, SO APPROACH CANNOT BE | | | VERIFIED. THE DETAIL PROVIDED LACKS DIMENSION TO SHOW | | | TOE AND KNEE CLEARANCE. SEE REQUIREMENTS FOR CHECK | | | WRITING SURFACES AND SALES COUNTERS, FBC A 904, 306. | | | | | | NEW COMMENT: | | | | | | 3. FBC 107, RETURN OLD SETS WHICH WERE REMOVED. DO NOT | | | REMOVE PLANS FROM THE DEPARTMENT. | | | | | | | | | |
|