| 2018-06-14 16:35:10 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE FOR THE LAVATORY IN THE |
| | BATHEOOM PER FBC ACC 606.2 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2. SHT. A-1 THE ADA TOILET ROOM DETAIL SHOWS THE DOOR |
| | SWING IN THE FLOOR PLAN SHOWS IT SWING OUT PLEASE |
| | CLARIFY. PER FBC ACC 603.2.3 |
| | |
| | 3. A WATER FOUNTAIN IS REQUIRED THE EXCEPTION IS ONLY |
| | FOR OCCUPANCY'S LIC AS RESTAURANT OR OCCUPANT LOADS15 |
| | OR UNDER. PER FBC PL TABLE 403.1 AND 410.2, 410.4 |
| | |
| | 4. A GREASE INTERCEPTOR IS REQUIRED FOR THR 3 |
| | COMPARTMENT SINK AND SERVICE SINK. PER FBC PL 1003.3.1 |
| | AND WPB UTILITIES DEPARTMENT FOR QUESTIONS PLEASE |
| | CONTACT JEFF ODOMS @ 561-822-2172 OR [email protected] |
| | |
| | 5. THE TOILET IS NOT VENTED NORMALLY IT WOULD BE VENTED |
| | BY THE LAVATORY. PER FBC PL 901.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |