| 2018-06-07 12:15:37 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050987 |
| | 6/7/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GARAGE AREA OF THE EXISTING BUILDING IS |
| | UNDERGOING A CHANGE OF OCCUPANCY FROM STORAGE TO |
| | MERCANTILE, AND THEREFORE MUST BE IN COMPLIANCE WITH |
| | THE FBC-17 ENERGY CONSERVATION CODE. REFER TO SECTION |
| | C505.1 AND SUBMIT AN ENERGY COMPLIANCE FORM IN |
| | ACCORDANCE WITH SECTIOMN C101.5.1 FBC EC. |
| | |
| | 2) M-2: THE SUBMITTED AC CALCULATIONS ARE INDICATING |
| | 75,136 BTUH OF HEATING REQUIRED WHICH EQUATES TO 22 KW, |
| | HOWEVER ONLY A 15 KW HEAT STRIP IS BEING PROVIDED PER |
| | THE SCHEDULE. |
| | |
| | 3) M-2: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY |
| | DUCT OF AHU-1- SECTION 606.2.1 FBC M. |
| | |
| | 4) M-1: INDICATE HOW THE THREADED RODS SUPPORTING AHU-1 |
| | ARE TO BE ATTACHED TO THE CONCRETE CEILING. |
| | |
| | 5) M-1 & M-2: THE DUCT HANGING DETAILS ARE FOR |
| | RECTANGULAR DUCT HOWEVER THE PLAN SHOWS ROUND TO BE |
| | INSTALLED- PLEASE REVISE THE DETAILS. |
| | |
| | 6) M-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADENOA |
| | FOR THE CONDENSER STAND. ALL SUBMITTALS MUST BEAR THE |
| | APPROVAL STAMP OF THE ENGINEER OF RECORD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |