| 2018-06-15 10:17:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT ON ROOF PER |
| | CODE. NEC 210.63 |
| | 2. PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62 |
| | 3. PANEL SCHEDULE SHOWS A 120/208 SERVICE AND SERVICE |
| | CALCULATION IS FOR 3 PHASE. RISER DIAGRAM SHOWS WIRING |
| | FOR A SINGLE PHASE SERVICE. PROVIDE CLARIFICATION AND |
| | CORRECTIONS AS NEEDED. NEC 215.5; WPB FBC 107.2.1 |
| | 4. NOTE UNDER PANEL SCHEDULE STATES THAT ALL 15 AND 20 |
| | AMP BREAKERS SHALL BE AFCI PROTECTED, WHICH IS NOT A |
| | CODE REQUIREMENT FOR THIS INSTALLATION. PLEASE CLARIFY |
| | AND/OR CORRECT. WPB FBC 107.2.1 |
| | 5. SOME LIGHTING IS SHOWN WITHOUT THE AUTOMATIC CONTROL |
| | REQUIRED. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING |
| | CONTROLS STIPULATED IN THE FBC ENERGY CODE. FBC EC |
| | C405.2 |
| | 6. PLUMBING COMMENTS STATE THAT A WATER FOUNTAIN IS |
| | REQUIRED. PROVIDE GFCI PROTECTION FOR DRINKING |
| | FOUNTAIN. THE GFCI DEVICE MUST BE READILY ACCESSIBLE. |
| | NEC 422.5, 422.52 |
| | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 8. PLAN SHOWS 2 DIFFERENT LOAD CALCULATIONS, ONE IN A |
| | BLOCK NOTE AND ONE IN PANEL SCHEDULE. PROVIDE ACCURATE |
| | LOAD CALCULATION INCLUDING ALL LOADS. WATER HEATER IS A |
| | CONTINUOUS LOAD. NEC 220, 422.13 |
| | 9. PROVIDE LIGHT FIXTURE SCHEDULE. PROVIDE CHART OF |
| | INTERIOR LIGHTING POWER ALLOWANCES EXPRESSED IN WATTAGE |
| | PER THE FBC ENERGY CODE IN RELATION TO THE WATTAGE OF |
| | THE CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC EC C405.4.2; WPB FBC 107.2.1 |
| | 10. SIGN CONTROLLER IS REQUIRED TO HAVE A DISCONNECT |
| | WITHIN SIGHT OF THE CONTROLLER. PROVIDE CORRECTION. NEC |
| | 600.6(A)(3) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |